Installation

Symmons Industries, Inc. 

 31 Brooks Drive 

 Braintree, MA 02184 

 (800)796-6667 

■ 

Fax: (800)961-9621

©2014 Symmons Industries, Inc.

 www.symmons.com 

 [email protected] 

  ZV-3010 REV D 05/27/14

Sizing Valve

For assistance in sizing and selection of the proper
valve, consult your local representative or Symmons
Customer Service.

Installing Valve

1) Flush piping thoroughly prior to installing.

2) Install valve so as to allow clearance for replacing 
    cartridge. Valve can be installed in any orientation.

valve body

 

(shown without

valve fittings)

safety cap

retaining nut

cartridge

3-1/2"

(89 mm)

Valve

clearance

3) Connect valve input/ouput to supply ports.
    a. Hot port marked (H)
    b. Cold port marked (C)
    c. Mixed output port marked (M)

Setting Valve Temperature

1) Turn hot and cold water supply on.

2) Open faucet to allow hot water to flow for a
    minimum of one minute. For two handle faucets
    turn on hot water only. For single handle faucets
    turn on to the hot position.

3) Remove the safety cap by inserting a small flat 
    tip screw driver into the wide slot at the base of 
    the cap and pry upward, then flip the safety cap
    over 180 degrees and fit onto the end of valve 
    spindle.

Temperature

Adjust

Safety Cap

4) Place thermometer in the outlet stream.  Measure
    and accurately set temperature.  Inlet temperature
    must be ± 10°F (5.55°C) of desired output.

5) To 

increase 

temperature turn safety cap 

    counter-clockwise. To 

decrease

 temperature turn

    safety cap clockwise.

     For single temperature applications adjust valve 
     outlet temperature with full flow of tempered
     water from fitting.

     For dual temperature applications open 
     approximately 50% of all faucets to their full hot
     position to ensure proper operating temperature
     at peak demand.

6) Remove safety cap from end of valve spindle and    
    flip over 180 degrees, then press cap down and
    snap back onto valve body to replace.

Note:

  Once the safety cap is snapped onto the 

           valve body the outlet temperature cannot be
           changed without repeating steps 2-6.

Warning:  Water temperatures in excess of
110°F (43°C) may cause scalding, or
severe injury!

Maxline

Operation & Maintenance Manual

7-210-CK

Отзывы: