098-00564-000 Revision A3 – July, 2013
TimeProvider 2300/2700 User’s Guide
45
Chapter 2 Installing
Making Ground and Power Connections
Figure 2-4.
Rack Mounting the TP 2300/2700
Making Ground and Power Connections
The DC version of the TimeProvider 2300/2700 has –48 VDC power connectors
which are located on the left side of the front panel (see
). Separate frame
ground terminals are on the left side and right side of the front panel.
The AC version of the TimeProvider 2300/2700 has a 120/240 VAC connector,
which is located on the left side of the front panel. (see
). Separate frame
ground terminals are on the left side and right side of the front panel.
Warning:
To avoid accidental power-up of the chassis, remove the A
and B fuses on the branch over-current protection unit before
beginning installation of the DC version of the TP 2300/2700. The unit
is not equipped with a power on/off switch.