097-55501-01 Revision M – January 2009
TimeHub 5500 User’s Guide 143
Chapter 4 Testing and Configuring the TimeHub
Installing Cards into the Front Panel
Installing the Clock Cards
To install the Clock cards, perform the following procedure.
illustrates the
front panel of the Clock card.
1. Locate switch S1 on the right side panel of the Clock cards (see
and
). If both Clock cards are the same (see the label on the front panel),
set bit 1 on both Clock cards to the ON position. If you are using mixed Clock
cards, set bit 1 on the quartz clock (55511 or 55512) to the OFF position; set bit
1 on the Rb clock (55513 or 55514) to the ON position. If you are using only one
clock in the shelf, set bit 1 to ON.
2. Insert either Clock card into the CLK 1 slot (located at the front of the shelf):
ensure that the card aligns properly with its mating backplane connector; push
the card into place until it is fully seated into the backplane connectors. Do not
tighten the captive screws at this time.
3. Insert the second Clock card into the CLK 2 slot: again, ensure that the card is
aligned properly and is fully seated. Do not tighten the captive screws at this
time.
If you are using only one Clock card, then you must provision the system for
single-clock operation (see
LED Sequence
The Warmup LED turns on when you insert the card into the shelf. When the
Warmup LED turns off on the Clock card(s) (from 2 to 20 minutes per Clock card),
the Freerun LED turns on. The Critical Alarm LED on the Management card turns
off and the Major Alarm LED turns on after the first Clock card enters the Freerun
state.
At least one of the inputs is qualified when one set of the INPUTS E, Q, and A LEDs
is lit on the Clock card. and the Fast Track LED turns on. After approximately 15
minutes the Holdover Available event is generated. If the input remains qualified for
the next 8 hours, the Fast Track LED turns off and the and the Tracking LED turns
on. If the input remains qualified for the next 32 hours, the Smart Clock Available
LED turns on. If the Clock card then goes into Holdover, the frequency stability of
the TimeHub is at its maximum.
To ensure that an input is qualified on a card, refer to the procedure in
Содержание TimeHub 5500
Страница 1: ...TimeHub 5500 User s Guide Revision M January 2009 Part Number 097 55501 01 ...
Страница 12: ...List of Figures 12 TimeHub 5500 User s Guide 097 55501 01 Revision M October 2008 ...
Страница 14: ...List of Tables 14 TimeHub 5500 User s Guide 097 55501 01 Revision M January 2009 ...
Страница 46: ...46 TimeHub 5500 User s Guide 097 55501 01 Revision M January 2009 Chapter 1 Description TimeScan THC Software ...
Страница 280: ...280 TimeHub 5500 User s Guide 097 55501 01 Revision M January 2009 Chapter 6 Specifications Factory Default Values ...