Chapter 3 ICS Command Reference
INPUT
194
SSU-2000e Technical Reference
12713140-003-2 Revision E.01 – January 2007
DISABLE
Disables the specified input port on a DS1, E1, CC, or Sine
Input module. This clears all alarms associated with an
input and disables setting of further alarms or use of the
input measurements.
SSM {4|5|6|7|8}
Sets the E1 SSM bit position. For use with the E1 Input
module.
PQL {1-16}
Sets the Priority Quality Level (PQL) for the specified input
port on any Input module.
GAIN{ON|OFF}
Enables or disables input gain setting. For use with the
DS1 or E1 Input module.
CSFLT {HIGH|LOW|OFF}
Sets Cesium fault logic level. For use with the
DS1, E1, or Sine Input module.
HIGH
Alarm active when the fault is a high logic level.
LOW
Alarm active when the fault is a low logic level.
OFF
Default. Cesium fault is ignored (not the AIS).
MTIE [{EL1|EL2|CL1|CL2}]{T10|T100|T1K|T10K|T100K}
value
Sets MTIE Limit 1 or Limit 2 for 10/100/1000/ 10 000/
100 000 seconds threshold. If L1 or L2 are not provided,
both limits are implied. The Limit Range is [0 – 60 000]. For
use with the DS1, E1, GPS, or Sine Input module.
EL1
MTIE Error Limit 1
EL2
MTIE Error Limit 2
CL1
MTIE Clear Limit 1
CL2
MTIE Clear Limit 2
T10
MTIE 10-second period
T100
MTIE 100-second period
T1K
MTIE 1000-second period
T10K
MTIE 10000-second period
T100K
MTIE 100000-second period
MTIE {PRS|DS1|G.811|G.823}
Sets MTIE Limit 1 or Limit 2 for predefined values
ANSI Specification –
PRS
,
DS1
ITU Specification –
G.811
,
G.823
{AIS|BPV|CRC|LOS|OOF}{SET|CLR} value
Sets Error Count (SET) or sets Clear Count (CLR) of the
specified input hardware alarm signal. Range is 1 to 100.
For use with the DS1 or E1 Input module.
FREQ {A|B}{SET|CLR|TAU} value
Sets Frequency limits on Clock A or Clock B. For use with
the DS1, E1, GPS, or Sine Input module.
SET
Sets Frequency Error Count
CLR
Sets Frequency Clear Count
TAU
Set frequency tau (default is 400), range is
10 to 1000