INSTALLATION INSTRUCTIONS

 FOR SYMCOM’S MOTORSAVER

 

MODEL 250600

CONNECTIONS

1.Mount the MotorSaver in a convenient location in or near the motor control  

   panel.  If the location is wet or dusty, then the MotorSaver should be 

   mounted in a NEMA 4 or 12 enclosure.
2.Connect the three lines of the motor’s three-phase power supply to L1, L2  

   and L3 on the MotorSaver’s terminal strip 
3.Connect the output relay to the circuitry to be controlled (see Figure No. 1  

   and Figure No. 2).

   A. To control a motor, connect the normally open contact in series with the 

        magnetic coil of the motor starter as shown in Figure 1.

   B. To sound an alarm, connect the normally closed contact in series with the  

        alarm as shown in Figure 2.

The Model 250600 is a three-phase voltage monitor designed to protect motors 

regardless of horsepower.  It will protect 50 to 60 Hz motors from damage 

caused by single phasing, phase reversal, voltage unbalance, low voltage and 

high voltage.  Added features include DPDT contacts and an adjustable restart 

delay.

Figure No.1: Typical Motor Control Wiring Diagram

Содержание MotorSaver 250600

Страница 1: ...ay to the circuitry to be controlled see Figure No 1 and Figure No 2 A To control a motor connect the normally open contact in series with the magnetic coil of the motor starter as shown in Figure 1 B To sound an alarm connect the normally closed contact in series with the alarm as shown in Figure 2 The Model 250600 is a three phase voltage monitor designed to protect motors regardless of horsepow...

Страница 2: ...o the nominal three phase secondary voltage of the potential transformer 2 TIME DELAY RESTART RESTART DELAY Rotate the RESTART DELAY to the desired position The restart delay is the time between the MotorSaver seeing acceptable power and the MotorSaver closing its output contacts The restart delay should be set appropriately for the individual application If the RESTART DELAY is in the MAN manual ...

Страница 3: ...3 There is a 50 50 chance of connecting L1 L2 and L3 correctly the first time Re apply the three phase power Red light is blinking After the motor has been previously running The incoming lines have been reverse phased The MotorSaver is preventing the motor from running backwards Correct the phase sequence Red light is blinking in this pattern The voltage is unbalanced or single phased Measure the...

Страница 4: ...t 93 High Voltage of setpoint Trip 110 Reset 107 Voltage Unbalance NEMA Trip 6 Reset 4 5 Trip Delay Time Low High Voltage Faults 4 Seconds Unbalance Phasing Faults 2 Seconds Restart Delay Time After a fault or complete power loss Adjustable Manual 2 300 Seconds Output Contact Rating DPDT Pilot Duty 480 VA 240 VAC General Purpose 10 A 240 VAC Transient Protection IEC 1000 4 5 1995 6 kv Power Consum...

Отзывы: