Страница 1: ...Swimming Pool Heat Pump User and Service Manual...

Страница 2: ......

Страница 3: ...t Pump 8 Troubleshooting 9 Exploded Diagram 10 Maintenance 11 WIFI function Alsavo Pro APP operation Thank you for using our swimming pool heat pump for your pool heating it will heat your pool water...

Страница 4: ...your Heat Pump Water connection assembly 48 3 mm pcs 2 User and service manual Draining plug pcs 2 Water drainage pipes pcs 2 10 meters signal wire pcs 1 Winter cover pcs 1 Anti vibration base pcs 4...

Страница 5: ...3 Model Swimmax 11iPS Swimmax 17iPS Model Swimmax 20iPS Swimmax 25iPS...

Страница 6: ...4 Model Swimmax 30iPS...

Страница 7: ...tion equipment and no fire source Heat pumps must be stored and transferred in vertical position in its original packaging If it is not the case it cannot be operated until a minimum period of 24H has...

Страница 8: ...4 3 74 0 63 4 96 0 78 C O P 7 1 4 6 7 2 4 6 7 2 4 6 7 2 4 6 7 2 4 6 7 2 4 6 General data Compressor type Inverter compressor Voltage V 220 240V 50Hz or 60Hz 1PH Rated current A 5 5 7 9 11 8 14 17 7 21...

Страница 9: ...assembly 2 sets Winter Cover 1 pc 4 2 The By Pass Kit The By Pass Kit is the essential accessory for the installation of your heat pump it is also a tool for the optimization of the heating of the wat...

Страница 10: ...ining plug Never overturn the heat pump it could damage the compressor Water Inlet outlet connection 1 Install the two joints like the picture shows 2 Screw them onto the water Inlet outlet connection...

Страница 11: ...ubbery that could block the air inlet Such locations impair the continuous supply of fresh air resulting in reduced efficiency and possibly preventing sufficient heat output 5 Location and connection...

Страница 12: ...the heat exchanger For this reason equipment of this sort must always be fitted in the piping on the downstream side of the heat pump and it is recommended to install a check valve to prevent reverse...

Страница 13: ...ration pump is turned off the unit should also turn off automatically 5 Allow the heat pump and the filtration pump to run 24 hours a day until the desired water temperature is reached The heat pump w...

Страница 14: ...d avoid excessive electrical contactor wear The unit will restart automatically after this time delay expires Even a brief power interruption will trigger this time delay and prevent the unit from res...

Страница 15: ...1 Inverter swimming pool heat pump wiring diagram Swimmax 07iPS Swimmax 11iPS Swimmax 17iPS Swimmax 20iPS Swimmax 25iPS Above electrical wiring diagram only for your reference please subject machine...

Страница 16: ...14 Swimmax 30iPS Above electrical wiring diagram only for your reference please subject machine posted the wiring diagram...

Страница 17: ...heat pumps It prevents remotely energizing unattended equipment and permits turning off power at the unit while the unit is being serviced 6 2 Installation of the display deportee Photo 1 Photo 2 Pho...

Страница 18: ...16 Connection to pilot the water pump Dry contact timer connection Dry contact pump connection...

Страница 19: ...ture directly Heating mode and Auto mode setting range 6 41 Cooling mode setting range 6 35 Press and at the same time to check water in temperature water out temperature and set temperature Remark 1...

Страница 20: ...atic mode it is useless to set parameter P1 Operation logic of Auto Mode T1 Water inlet temperature Tset set temperature 28 NO Condition Current working Status Water inlet Temperature Working mode 1 W...

Страница 21: ...5 Piping temp 30 70 flash if Real value 9 d6 Gas exhaust temperature 0 C5 125 Real testing value d7 Step of EEV 0 99 N 5 d8 Compressor running frequency 0 99Hz Real testing value d9 Compressor current...

Страница 22: ...valid 7 2 9 Time setting Timer setting Select and press to enter press again to Timer on Timer off setting Code Name Scope Default Remark P0 Mandatory defrosting 0 1 0 0 Default normal operation 1 man...

Страница 23: ...21 Press to enter and and to select Timer on or Timer off Press to select on off and press or to set the time Press to save the setting Long press for 5 seconds to set the current time...

Страница 24: ...g of the sensors Exhaust piping sensor failure T6 PP06 1 The sensor in open or short circuit 2 The wiring of sensor is loose 1 Check or change the sensor 2 Re fix the wiring of the sensors Antifreeze...

Страница 25: ...ter flow 3 Piping system has been blocked 4 Exhaust temp Sensor failure 1 Check the high pressure gauge if too low fill with some gas 2 Check the waterway system and filtration pump 3 Check the piping...

Страница 26: ...oil accumulation lead to the current becomes larger 4 Compressor or driver board damaged 1 Program error turn off electricity supply and restart after 3 minutes 2 Change driver board 3 Check compress...

Страница 27: ...DC fan motor failure EE17 1 DC motor is damaged 2 Main board is damaged 3 The fan blade is stuck 1 Detect DC motor replace with a new one 2 Change a new main board 3 Find out the barrier and work it o...

Страница 28: ...ck the compressor or change a new one Ambient Temperature device failure on Driver board EE24 Ambient Temperature device failure Change driver board or main board Compressor phase failure EE25 Compres...

Страница 29: ...han the set temperature over 7 controller displays PP11 for water over cooling protection EE04 Water Overheating Protection PP11 Water Overcooling Protection For example as below Mode Output water tem...

Страница 30: ...de Condition Tset Setting water temp T1 Inlet water temp Example Tset 28 Water pump working logic Heating mode T1 Tset 0 5 and last for 30 min T1 27 5 last for 30 minutes If heat pump enter standby mo...

Страница 31: ...e the wrong mode 2 Figures show defects 3 Controller defect 1 Adjust the mode to proper running 2 Replace the defect LED wire controller and then check the status after changing the running mode verif...

Страница 32: ...30 9 Exploded Diagram 7 Exploded Diagram Mode Swimmax 07iPS...

Страница 33: ...Drainage plug 13 Electric box 41 Water inlet temp sensor T1 TH6 14 Left panel 42 Exchanger temperature sensor clip 15 Isolation panel 43 Right panel 16 Reactor 44 Terminal board 17 Compressor 45 Press...

Страница 34: ...32 Model Swimmax 11iPS Swimmax 17iPS...

Страница 35: ...board cover 11 Pillar 41 Terminal board 12 Fan motor support 42 Water outlet temp sensor T2 TH5 13 Top frame 43 Water flow switch 14 Reactor 44 Gas return piping 15 Isolation panel 45 Low pressure swi...

Страница 36: ...34 Model Swimmax 20iPS Swimmax 25iPS...

Страница 37: ...ng 13 Back grill 44 Discharge pipe 14 Waterproof controller box 45 Sensor holder 15 Pipe 46 Pipe 16 Controller box cover 47 Evaporator pipe 17 Electric box cover 48 Distribution piping 18 Base tray 49...

Страница 38: ...36 Model Swimmax 30iPS...

Страница 39: ...flow switch 19 Waterproof controller box 58 Water outlet temp sensor T2 TH5 20 Left panel 59 Exchanger temperature sensor clip 21 Front grill 60 Titanium heat exchanger 22 Front panel 61 Water connect...

Страница 40: ...the damage of the unit 3 Only a qualified technician is authorized to operate the cooling system pressure You should drain the water from the heat pump if it will stop running for a long time especial...

Страница 41: ...display first then enter the current WIFi password The display will show F1 1 F1 2 until F1 6 which means the connect is OK If the connection fails the APP will indicate Failed to connect device Nickn...

Страница 42: ...40...

Страница 43: ...e there modes Auto mode cooling or heating for the invertboost unit Click its icons to switch Auto mode heating cooling 3 Timer setting Click it turns Timer on and off will be activated together Then...

Страница 44: ...42 4 Parameter checking and setting Click Parameter then enter the password 0757...

Страница 45: ...des optional for water pump operation 1 Always running 0 Depends on the running of compressor 2 Inlet water temperature calibration 9 0 to 9 0 3 Temperature unit or 4 When you want to reset to factory...

Страница 46: ...n heating or cooling mode there are 3 running modes Silent Smart Powerful for options While in Auto mode its default running mode is Smart 6 Malfunction If error occurs the malfunction icon turns red...

Страница 47: ...spondingly changes after letting go When the setting water temperature on the display changes it will be synchronously updated to the APP 8 Check device information In the main interface click the upp...

Страница 48: ...46...

Страница 49: ...47...