Installation

The air diffuser is normally suspended from the ceiling. 
An M8 pop nut, i.e. a threaded grommet that facilitates 
installation, is in the centre of the top of the air diffuser. 
On the size 315 and 400 air diffusers, there are two M8 
pop nuts for more stable mounting, see figure 1 and 3. 

Commissioning

Commissioning should be carried out with the diffuser 
face mounted. Pull the measuring tubes and the damper 
adjustment cords out of the air diffuser through one 
nozzle in the diffuser face. Then connect the manome-
ter to the correct measuring tube(s): two blue tubes for 
supply air and one transparent tube for extract air. The 
rated coefficient of performance of the air register can be 
used in a calculation to determine the required commissi-
oning pressure. Conclude commissioning by adjusting the 
damper to the correct blade position, tie a commissioning 
knot in the damper cords to indicate the damper position. 
See Figure 1.
The K-factor is specified on the product’s identification 
label and last in these instructions.

Maintenance

•  Clean the air diffuser if needed with lukewarm water 

and dishwashing detergent added.

•  The duct system can be accessed and lightly pulling 

the spring-loaded diffuser front downwards and then 
tilting, see figure 2.

•  Dismantle the perforated air distribution plate located 

on the inlet as shown in figure 4.

•  Loosen the damper in the inlet from its bayonet fastening 

by rotating to the side.

Length of straight duct

Type of obstruction upstream of
EAGLE Free

Length of straight duct 

upstream of the EAGLE 

Free

m

2

 = 5%

m

2

 = 10%

One 90° bend

3 ·Ød

2 ·Ød

Two 90°bends in the same plane

4 ·Ød

2 ·Ød

Two 90° bends in alignment at 
right angles to one another.

4 ·Ød

2 ·Ød

One 45° damper

6 ·Ød

3 ·Ød

One T-piece

4 ·Ød

3 ·Ød

m

2

 = accuracy of the method according to NVG’s report T32:1982

Figure 1. Installation. Commissioning. Maintenance.

q

 = flow reading l/s

p

 = current pressure reading (Pa)

k

 = commissioning factor

k-factor

k

p

q

=

k

p

q

=

(    )

2

EAGLE Free x 

Tomelilla

Sweden

XXX

k = XX

k

p

q

TILLUFT / SUPPLY AIR

TILLUFT / SUPPLY AIR

FRÅ

NLU

FT /

 EXTR

ACT AI

R

Figure 2. Spring-loaded diffuser front.

EAGLE

 Free g

Installation – Commissioning – Maintenance

20201008

Содержание EAGLE Free g

Страница 1: ...oduct s identification label and last in these instructions Maintenance Clean the air diffuser if needed with lukewarm water and dishwashing detergent added The duct system can be accessed and lightly pulling the spring loaded diffuser front downwards and then tilting see figure 2 Dismantle the perforated air distribution plate located on the inlet as shown in figure 4 Loosen the damper in the inl...

Страница 2: ...Figure 3a Alternative installation Figure 3b Extra M8 pop nut size 315 and 400 Applies only for size 315 400 We recommend wearing gloves as there is a risk of cut injuries to the hands fingers EAGLE Free 2 Swegon reserves the right to alter specifications 20201008 ...

Страница 3: ... in the sleeve plate The damper is turned anticlockwise and pulled out The number holes in the damper must correspond with the number of holes in the sleeve plate We recommend wearing gloves as there is a risk of cut injuries to the hands fingers 3 20201008 Swegon reserves the right to alter specifications EAGLE Free ...

Страница 4: ...measuring tubes 2 EAGLE F extract air Size k factor Tube colour 100 5 7 Transparent 125 9 0 Transparent 160 15 2 Transparent 200 24 3 Transparent 250 32 9 Transparent 315 49 4 Transparent 400 68 4 Transparent Number of measuring tubes 1 Figure 6 EAGLE Free Dimensions and weights Size A B C D E Number of nozzles Weight kg 100 304 192 118 99 96 19 2 7 125 380 217 210 124 108 31 3 9 160 456 252 220 1...

Отзывы: