We reserve the right to make changes without any prior notice.
Translation from original instructions
6.3.4 Anti-vibration mounts
In order to reduce vibrations transmitted to the structure, it is advisable to install the unit on rubber or spring anti-vibration
mounts, supplied as an accessory and to be requested when placing the order.
The dimensional diagram with footprint shows the position and load of each anti-vibration mount.
The anti-vibration mounts must be fixed on before positioning the unit on the ground.
To install the anti-vibration mounts, see the instructions attached to the accessory.
When fixing the anti-vibration mounts, the unit should be lifted off the ground by no more than 200 mm and
no parts of the body should be placed under the unit.
6.3.4.1
Rubber anti-vibration mounts
The anti-vibration mount consists of an upper metal bell in which there is a screw for fixing it to the base of the unit. The
anti-vibration mount is fixed to the base through the two holes on the flange. The flange of the anti-vibration mount bears a
number (45,60,70 ShA) that identifies the hardness of the rubber support.
Fig. 1 Rubber/metal anti-vibration mounts
6.3.5 Noise attenuation
The units are designed and built paying particular attention to keeping down noise emission during operation.
Correct installation for both the place and the components, as shown in the relevant chapter, prevents resonances, reflections
and vibrations that can be particularly bothersome.
If, after following the instructions above, further attenuation is required, the use of acoustic barriers is a valid solution.
It is essential to be careful that any work done to soundproof the unit does not affect its correct installation or its correct
operation.
Do not restrict the service spaces and do not install covers that may create recirculation between the air supply line and the
intake line.
6.3.6 Minimum distances
The service spaces to be guaranteed are shown on the dimensional drawings of the unit.
It is essential to ensure an adequate volume of air in both the intake line and the delivery line of the external coil.
It is very important to avoid recirculation between suction and delivery, as this would lower the performance of the unit or
even stop its normal operation.
The presence of very high walls near the unit will impair its correct operation.
In configurations with external units installed side by side, the min. distance between two units must be as shown in Fig. C.2.
In any case, we recommend leaving a large enough space between the units to allow removal of their larger components,
if necessary.
Содержание BlueBox Tau SKY Hi HP
Страница 1: ...Tau SKY Hi HP EN 05 08 2020 Installation use and maintenance manual...
Страница 64: ...64 We reserve the right to make changes without any prior notice Translation from original instructions A 4...
Страница 69: ...69 We reserve the right to make changes without any prior notice Translation from original instructions C 4...
Страница 74: ...74 We reserve the right to make changes without any prior notice Translation from original instructions E 1 E 2...
Страница 75: ...75 We reserve the right to make changes without any prior notice Translation from original instructions E 3 E 4...
Страница 76: ...76 We reserve the right to make changes without any prior notice Translation from original instructions E 5 E 6...
Страница 77: ...77 We reserve the right to make changes without any prior notice Translation from original instructions E 7 E 8...
Страница 87: ...87 We reserve the right to make changes without any prior notice Translation from original instructions...
Страница 88: ...UM_0000 Tau SKY Hi HP EN 05 08 2020 rev01...