AMI Codes-II CC
Program List and Explanations
A-96.250.581 / 220616
97
5.3.2 and 5.3.3
Relay 1 and 2:
The contacts can be set as normally open or nor-
mally closed with a jumper. See
.
The function of relay contacts 1 or 2 are defined by the user.
NOTICE:
The navigation in the menu <Relay 1> and <Relay 2>
is equal. For reason of simplicity only the menu numbers of
Relay 1 are used in the following.
1
First select the functions as:
- Limit upper/lower,
- Control upwards/downwards,
- Timer
- Fieldbus
- End of Batch (relay 2 only)
2
Then enter the necessary data depending on the selected func-
tion.
When the relays are used as upper or lower limit switches, program
the following:
5.3.2.20
Parameter:
select a process value
5.3.2.300
Setpoint
: If the measured value rises above respectively falls below
the set-point, the relay is activated.
5.3.2.1
Function = Limit upper/lower:
Parameter
Range
Free av. chlorine
0–10 ppm
Total chlorine 1
0–10 ppm
Total chlorine 2
0–10 ppm
Calc. monochl.
0–10 ppm
Calc. comb. cl.
0–10 ppm
Calc. dichloramine
0–10 ppm
Temperature
-30 to +120 °C
Sample flow
0 –600 B/s
pH
0–14 pH