Swagelok PRS4 Скачать руководство пользователя страница 7

 

Maintenance  

 

WARNING 
Incorrect or improper repair or servicing of this product can cause serious personal injury and 
property damage. 

 

All repairs, servicing, and testing of this product must be performed by competent personnel. 

Following any maintenance of the regulator, it is recommended that the product be tested for operation 
and leakage. 

The product should be checked periodically for proper and safe operation. 

It is the user’s sole 

responsibility to determine the frequency of maintenance based on the application. 

To reduce maintenance related system downtime to a minimum, either during commissioning or normal 
operation, Swagelok recommends having maintenance kits readily available on site. The need for 
maintenance kits is particularly important during the commissioning phase of a system installation due to 
residual assembly debris remaining in the system. Such debris can cause a seat leak in the regulator, 
resulting in components needing to be replaced. 

 

Required Tools for Maintenance 

 

Smooth-jawed vise 

 

 

C-ring pliers

 

 

10 mm socket

 

 

Seat retainer insertion tool

RHPS-4-SEAT-TOOL 

 

14 mm open-ended 

wrench

  

 

Calibrated torque wrench up 
to 37 lbf·ft (50 N·m) 

 

19 mm open-ended 

wrench

  

25 mm crows foot

  

 

Lubricant (included in kit): 
Krytox® 240 AC

 

 

Adhesive (not included in 
kit): 
Loctite® 5045, 4052 or 243 

 

36 mm crows foot

 

45 mm crows foot

 

5 mm hex drive

 

 

Liquid leak detector 

 

  PRS8 series only 

  PRS4 series only 

Table 1 

Содержание PRS4

Страница 1: ...PRS4 and PRS8 Pressure Reducing Regulator User Manual Read the complete manual before installing and using the regulator...

Страница 2: ...dia should be free of excessive moisture to prevent icing at high flow Always wear the appropriate protective clothing including safety glasses gloves etc if required Follow the applicable safety and...

Страница 3: ...Operation 6 Points of Attention Before Operation 6 Adjusting the Set Pressure 6 Maintenance 7 Required Tools for Maintenance 7 Points of Attention Before Removal from the System 8 Removal from the Sys...

Страница 4: ...oduct failure Standard Features Threaded construction Stainless steel as standard Fully serviceable Diaphragm sensing Bottom mounting Additional Options The regulator is available with the following o...

Страница 5: ...s materials of construction and the system media Installation Verify that the regulator its connections and any accessories are undamaged Verify that the regulator and any accessories are suitable for...

Страница 6: ...sure may result in a fall of the outlet pressure This is usually referred to as inlet dependency or Supply Pressure Effect SPE This phenomenon does not indicate a problem with the regulator Adjusting...

Страница 7: ...ng or normal operation Swagelok recommends having maintenance kits readily available on site The need for maintenance kits is particularly important during the commissioning phase of a system installa...

Страница 8: ...or toxic If required take the necessary safety precautions to ensure a safe workspace and your personal safety CAUTION The product can be hot or cold depending on the environmental temperature and the...

Страница 9: ...ide C1 12 Washer C1 13 Hex nut C1 3 7 5 14 Clamp ring C1 15 Set spring C1 C4 16 Spring guide C1 Lubricate central recess 17 Ball C1 Lubricate 18 Spring housing N A 37 50 Lubricate threads 19 C ring D1...

Страница 10: ...10 PRS4 Series Exploded View Fig 1...

Страница 11: ...11 PRS4 Series Section View Fig 2...

Страница 12: ...12 PRS8 Series Exploded View Fig 3...

Страница 13: ...13 PRS8 Series Section View Fig 4...

Страница 14: ...e 11 6a PRS4 series Remove the seat retainer 8 using the seat retainer insertion tool Remove the seat 7 seat O ring 6 poppet 5 and poppet spring 3 from the body 1 6b PRS8 series Remove the seat retain...

Страница 15: ...guide 11 12 Lightly lubricate the spring housing threads 18 and screw it onto the body 1 Torque to 37 lbf ft 50 N m PRS8 Series 1 Secure the body 1 in a vise 2 Fit the poppet O ring 4 onto the poppet...

Страница 16: ...ly 14 5 psig 1 bar on the regulator and close the downstream shutoff valve 4 Monitor the outlet pressure An increase in pressure over time indicates a seat leak 5 Repeat the procedure with the highest...

Страница 17: ...er than the desired set pressure The outlet pressure rises too much when going from a dynamic to a static situation There is too much flow in the dynamic situation A larger regulator or parallel regul...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...e Swagelok Limited Lifetime Warranty For a copy visit swagelok com or contact your authorized Swagelok representative Swagelok Snoop TM Swagelok Company Loctite TM Henkel Corp Krytox TM The Chemours C...

Отзывы: