Interfaces of the Device
4-10
4.2.1.2
Cable
The cable must have the following characteristics:
The maximum cable length depends on the baud rate used.
4.2.1.3
Termination
Terminate the CAN bus at both ends by terminating resistors (120 Ohm).
4.2.1.4
Diagnostic
A diagnostics LED is located at the rear of the operating device. The LED shows a
state of the bus system.
Figure 4-9
Arrangement of the CAN diagnostics LED
The diagnostics LED at the operating device has the following functions:
A shielded twisted-pair cable (cable type LiYCY-TP) complying with ISO 11898 must
be used.
Table 4-10
Cable characteristics CAN
Parameters
Value
Impedance
Min.: 108 Ohm
Nom.: 120 Ohm
Max.: 132 Ohm
Specific Resistance
70 mOhm/m
Specific Line Delay
5 ns/m
Table 4-11
Baud rate CAN
Baud rate
Cable length
20 kBit/s
1000 m
125 kBit/s
500 m
250 kBit/s
250 m
500 kBit/s
100 m
1000 kBit/s
25 m
Table 4-12
Function of the CAN diagnostics LED
Color
State
Function
Green
Off
Terminal Disconnected from Bus
Green
On
Communication Active
Green
Flashing
Sporadic Bus Error