PIR & Ultrasonic Occupancy Sensor

CDL-608C24  embodies  the  technology  of  infrared  and  ultrasonic  motion 
detection into one easy-to-install occupancy sensor. Mounted at a height 
of  2.4m,  this  sensor  detects  people  moving  within  8m  diameter  of  a  full 
circular coverage area.

CDL-608C24  can  be  surface  mounted  or  flush  mounted  for  an  attractive, 
un-obstructive appearance. One or many sensors can be connected with 
Suren's (or compatible) power packs to control a wide range of load types, 
including lighting or HVAC devices.

Operation

Initialization:

 

The sensor becomes operational 30 seconds after power is supplied.

Detection and Activation:

 

When a person enters a room, the sensor detects major body motion and 
turns the light on. The light is kept on even as smaller body movement is 
detected.  The  sensor's 

Detection  Sequence  Logic

  (DSL)  minimizes 

false triggering by adjusting detection sensitivity based upon sequence of 
occupancy  events.  The 

Sunset  Sensor

  provides  additional  control  such 

that  lighting  is  not  activated  when  there  is  sufficient  brightness  in  the 
area.
 

De-Activation (Normal Occupancy Mode):

 

When  motion  is  no  longer  detected,  the  sensor  turns  the  light  off  after  a 
set time delay (Delayed-Off Time).

Walk-thru Mode:

 

The  walk-through  feature  is  useful  in  areas  that  are  momentarily 
occupied,  e.g.  hallway.  If  the  sensor  detects  no  movement  for  more  than 
10  seconds  light  was  turned  off,  it  will  apply  a  Delayed-Off  Time  of  2.5 
minutes. If the sensor detects movement less than 10 seconds after light 
was turned off, it will next turn the light off based upon the set time delay.

Installation

Accessories:

·

Brackets, screws and wall plugs for surface mount in solid ceiling

·

Spring clips for flush mount in drop ceiling

·

Infrared zone mask

Location: 

·

Determine the number of sensors required to cover the floor area

·

Install  the  sensor  near  work  area  where  walk-path  cuts  across  radial 
lines, not towards the sensor

·

Do not install the sensor near ventilation outlet

·

Avoid  facing  the  ultrasonic  transceivers  to  each  other  to  minimize 
interference

Procedure: 

·

Prepare sensor mount. See illustration in the next page

·

Connect the sensor as shown in the wiring diagram. Make sure power 
supply is turned off

·

Make sure there are no wiring exposed before mounting the sensor

·

Mount the sensor and turn on the power supply

·

Open the cover, review settings and change if necessary. See Settings 
section

·

Initiate test mode, replace the cover and conduct walk-test

Walk-Test: 

·

Toggle dip switch B3 (Off-On-Off) to enter test mode. If B3 is already in 
the  On  position,  moving  it  to  the  Off  position  will  also  activate  test 
mode

·

Amber  LED  will  flash  once  every  second  when  the  sensor  is  in  test 
mode

·

During this time, the sensor will turn the light off after 5 seconds if there 
are no movement

·

Test movement at entry point, walk path and occupancy area

·

Sensor will exit test mode after 15 minutes

LED Indicator: 

·

LED indicator can be enabled or disabled by dip switch setting

·

Recommended for troubleshooting

·

Red LED indicates motion detected by infrared sensor

·

Green LED indicates motion detected by ultrasonic sensor

Top view

0

m

m

2

2

0

4

4

2

2

4

4

PIR Optical View Pattern                     Ultrasonic Detection Pattern

CDL-608C24

Operation and Specification

SURE

N

 ©2011 SUREN Systems, Ltd.. All rights reserved. SUREN™

SUREN Part no.: N-ML00-0045-01-1

 

Rev.3

Printed in China

w w w . s u r e n s y s t e m s . c o m

 

Wiring Diagram:

 

Detection Area:

Side view

Detection range

at 2.4m height  

 

 

 

 

 

 

 

 

m

2

2

0

4

4

Light

Live

Neutral

+

+

+

Line
85 - 277 V AC
50/60Hz

Load

-

-

-

Control

Control

Control

Sensor 1

Sensor 2

Sensor N

Power
Pack

Note: more than one sensor can be connected
to a power pack.

Power Supply:

 

24 V DC (Power pack PS-124 
or PS-224 required)

Power Consumption:

 

0.96 W

Control Signal Output:

24 V DC, 15 mA

P

IR Sensor:

 

Pyroelectric

,

2-element

Ultrasonic Frequency:

 

40 Khz

H

ousing Material:

High-impact ABS

Dimension: 

110mm Diameter x 56 mm Height

Operating Temperature Range: 

o

o

-40  to 55  C

RF Immunity:

20 V/m 10-1000 Mhz; 10 V/m 1-2 GHz

Approvals: 

   

 

Specification