background image

CPL-312C24

Operation and Specification

SURE

N

 ©2011 SUREN Systems, Ltd.. All rights reserved. SUREN™, HDIR™ are trademarks of SUREN.

SUREN Part no.: N-ML00-0065-11-1

 

Rev.1

Printed in China

w w w . s u r e n s y s t e m s . c o m

T M

Patented HDIR  Presence Sensor

CPL-312C24  is  a  motion  sensor  with  SUREN's  proprietary  8-element 
pyros and multi-segment lens array. Mounted at a height of 2.4m, CPL-
312C24 not only offers detection of minor motion, e.g. hand movement, 
within the 6m diameter area but also detection of people walking within 
the area of 12m diameter.

CPL-312C24 can be surface mounted or flush mounted for an attractive, 
un-obstructive  appearance.  One  or  many  sensors  can  be  connected 
with Suren's (or compatible) power packs to control a wide range of load 
types, including lighting or HVAC devices.

Operation

Initialization:

 

The sensor becomes operational 30 seconds after power is supplied.

Detection and Activation:

 

When  a  person  enters  a  room,  the  sensor  detects  major  body  motion 
and  turns  the  light  on.  The  light  is  kept  on  even  as  minor  motion,  e.g. 
hand  movement  is  detected.  The  sensor's 

Detection  Sequence  Logic

 

(DSL)  minimizes  false  triggering  by  adjusting  detection  sensitivity 
based upon sequence of presence events. The 

Sunset Sensor

 provides 

additional  control  such  that  lighting  is  not  activated  when  there  is 
sufficient brightness in the area.
 

De-Activation (Normal Occupancy Mode):

 

When motion is no longer detected, the sensor turns the light off after a 
set time delay (Delayed-Off Time).

Walk-thru Mode:

 

The  walk-through  feature  is  useful  in  areas  that  are  momentarily 
occupied, e.g. hallway. If the sensor detects no movement for more than 
10  seconds  light  was  turned  off,  it  will  apply  a  Delayed-Off  Time  of  2.5 
minutes. If the sensor detects movement less than 10 seconds after light 
was turned off, it will next turn the light off based upon the set time delay.

Installation

Accessories:

·

Brackets, screws and wall plugs for surface mount in solid ceiling

·

Spring clips for flush mount in drop ceiling

·

Infrared zone mask

Location: 

·

Determine the number of sensors required to cover the floor area

·

Install the sensor near work area where walk-path cuts across radial 

lines, not towards the sensor

·

Do not install the sensor near ventilation outlet

Procedure: 

·

Prepare sensor mount. See illustration in the next page

·

Connect  the  sensor  as  shown  in  the  wiring  diagram.  Make  sure 

power supply is turned off

·

Make sure there are no wiring exposed before mounting the sensor

·

Mount the sensor and turn on the power supply

·

Open  the  cover,  review  settings  and  change  if  necessary.  See 

Settings section

·

Initiate test mode, replace the cover and conduct walk-test

Walk-Test: 

·

Toggle dip switch B3 (Off-On-Off) to enter test mode. If B3 is already 

in the On position, moving it to the Off position will also activate test 
mode

·

Amber  LED  will  flash  once  every  second  when  the  sensor  is  in  test 

mode

·

During  this  time,  the  sensor  will  turn  the  light  off  after  5  seconds  if 

there are no movement

·

Test movement at entry point, walk path and presence area

·

Sensor will exit test mode after 15 minutes

LED Indicator: 

·

LED indicator can be enabled or disabled by dip switch B2

·

Recommended for troubleshooting

·

Red LED indicates motion detected by infrared sensor

 

 

Detection range

at 2.4m height  

 

 

 

 

 

 

 

 

Detection Area:

0

m

m

0

6

3

3

6

3

3

6

6

Top view

Side view

PIR Optical View Pattern

Body motion

Minor motion
e.g. hand 
movement

m

0

6

3

3

6

Power Supply:

 

24 V DC (Power pack PS-124 
or PS-224 required)

Power Consumption:

 

0.22 W

Control Signal Output:

24 V DC, 15 mA

PIR Sensor:

 

Pyroelectric

,

8-element

Housing Material:

High-impact ABS

Dimension: 

110mm Diameter x 56 mm 
Height

Operating Temperature 
Range: 

o

o

-40  to 55  C

RF Immunity:

20 V/m 10-1000 Mhz; 10 
V/m 1-2 GHz

Approvals: 

    

Specification

Отзывы: