2.0 Introduction
- 12 -
For ULC Installations the equipment must be installed in accordance with the requirements of ULC-S561 and ULC-S301 Standards and the authority
having jurisdiction. SG-System 5 with SG-DRL5/DRL5E/DRL5-2L PSTN line cards is ULC listed for passive communication channel security levels
P1-P3 when used in conjunction with compatible alarm systems using Industry Open SIA standard communication formats Contact ID or SIA.
This product has been approved by the California State Fire Marshal (CSFM) pursuant to section 13144.1 of the California Health and Safety Code.
See CSFM Listing No. 7300-1273:0157 for allowable values and/or conditions for use concerning material presented in this document. The approval is
subject to reexamination, revision and possible cancellation.
2.3.2 UL864 programming requirements
NOTE: Users, Installers, Authorities having Jurisdiction and other involved parties; this product incorporates field programmable soft-
ware. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarms
Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.
SG-CPM5 - UL864 programming requirements
Opt #
Program option
Permitted in UL864? (Y/N) Possible settings Settings permitted (UL 864)
202
Buzzer
N
Enabled/Disabled
Enabled
411
Heartbeat Timer
Y
00-FF
Not Allowed 00
601
CPM5 1 Fan Trouble
N
Enabled/Disabled
Enabled
602
CPM5 2 Fan Trouble
N
Enabled/Disabled
Enabled
603
PSU 1 Trouble
N
Enabled/Disabled
Enabled
604
PSU 2 Trouble
N
Enabled/Disabled
Enabled
609
UPS AC 1 Trouble
N
Enabled/Disabled
Enabled
610
UPS AC 2 Trouble
N
Enabled/Disabled
Enabled
611
UPS Battery 1 Trouble
N
Enabled/Disabled
Enabled
612
UPS Battery 2 Trouble
N
Enabled/Disabled
Enabled
615
SG-Serial Automation Sec 1 Trouble
N
Enabled/Disabled
Enabled
617
Serial CPM 1 Printer 1 Trouble
N
Enabled/Disabled
Enabled
618
Serial CPM 2 Printer 1 Trouble
N
Enabled/Disabled
Enabled
619
Serial CPM 1 Printer 2 Trouble
N
Enabled/Disabled
Enabled
620
Serial CPM 2 Printer 2 Trouble
N
Enabled/Disabled
Enabled
621
SG-TCP Automation Pri - Trouble
N
Enabled/Disabled
Enabled
631
SG-TCP Automation Sec - 1 Trouble
N
Enabled/Disabled
Enabled
665
TCP Printer Pri - 1 Trouble
N
Enabled/Disabled
Enabled
675
TCP Printer Sec - 1 Trouble
N
Enabled/Disabled
Enabled
SG-DRL5-IP
Opt #
Program option
Permitted in UL 864 (Y/N)
Possible
settings
Settings permitted (UL 864)
221
Transmitter Absent Debounce Time
N
5-65535
200
222
Transmitter Restoral Debounce Time
N
5-65535
200
301
Transmitter Unencrypted Trouble
N
Enabled/Disabled
Enabled
302
Unknown Account Trouble
N
Enabled/Disabled
Enabled
303 Supervised Accounts Exceeded Trouble
N
Enabled/Disabled
Enabled
SG-DRL5-2L/DRL5E/DRL5
Opt #
Program option
Permitted in UL 864?
(Y/N)
Possible set-
tings
Settings permitted (UL
864)
104/204
2-Way Activation Time
N
00-FF
00
12F/22F
4- and 5-digit Account Codes to Activate 2-Way
Audio
N
00-FF
00
17B/27B
3-Digit Account Codes to Activate 2-Way Audio
N
00-FF
00
17C/27C
Alarm Codes to Activate 2-Way Audio
N
00-FF
00
17D/27D
Supervised Accounts Exceeded Trouble
N
00-FF
00