Receiver Setup and Operation
Sur-Gard recommends testing the receiver before actual installation. Becoming familiar with the connections and setup of the unit on the
workbench will make final installation more straightforward.
The following items are required:
• IEC power supply cord
• One telephone line
• One or more dialer or digital control panel(s)
1.
Unpack the components for the SG-System III.
NOTE: Carefully unpack the receiver and inspect for shipping damage. If there is any apparent damage, notify
the carrier immediately.
2.
Unscrew the front thumb screws and open the front plates.
NOTE: Before inserting the SG-CPM3, connect the ribbon cable from the SG-UIB3 board. Before inserting the
SG-PSC3 connect the LCD power cable.
3.
Starting with slot 1, insert all cards in the rack to their appropriate positions. Ensure that there are no open slots between cards. (refer to
figure 1-2).
4.
Insert the SG-PSU3 into the rack and screw in the thumb screw.
5.
Connect a telephone line to the corresponding line on the SG-BP3.
6.
Connect the main power using a standard computer IEC cable (not supplied).
7.
The LCD will power up and display internal troubles (e.g., printer, computer, telephone line fault). The SG-DRL3 that has the telephone
line connected to it will have its red LED off. If the LED is on, make sure the telephone line is connected to the correct port.
8.
Press the ACK button until all of the initial signals have been acknowledged (ACK button has stopped flashing and the buzzer has been
silenced).
NOTE: Internal diagnostics may require more than one minute during the power up sequence.
9.
Send a signal from a control panel to the receiver. The signal will be displayed on the LCD. Press the [ACK] button to silence the buzzer
and clear the signal from the LCD.
Description (Operation)
Operation with Default Programming
Without any changes to the factory default programming, the receiver operates as indicated below:
• Answers incoming calls on the first ring
• Sends the following handshake order:
• Receives most communication formats, except for 3/2, 3/1 checksum, SKFSK, 4/2 extended, and 4/2 checksum (see Option 95).
• The above formats can be manually selected
• Signals can be displayed on the debug output computer as they are received. The signals are then sent to the printer and computer con-
nected to serial port COM1 or to the 10/100BaseT. The default event codes described in the
SG-DRL3 Library Decoding and Event
Codes Table
will be used with the Sur-Gard automation communication protocol to send signals to the computer, if connected.
• If a computer is not connected press the [ACK] button on the SG-CPM3 to silence the buzzer and to clear the alarm(s) from the LCD
display.
1
2
3
4
5
6
2300 Hz
1400 Hz
Dual-tone
SIA FSK
ITI, Modem IIE/IIIa2
Modem II
Содержание SG-System III
Страница 22: ...Line Card In This Chapter Standby Mode on page 19 Line Fault on page 21...
Страница 92: ...In this Chapter Options 00 47 on page 90 SG DRL3 IP Programming...
Страница 100: ...Printer Words...
Страница 105: ...Telco Connector Pin Outs...
Страница 107: ...DEC HEX BIN Conversion Chart...
Страница 109: ...ASCII Character Chart...
Страница 111: ...SG DRL3 SG DRL3E SG DRL3 2L Communication Formats...
Страница 113: ...Ports...
Страница 115: ...Events Messages...
Страница 124: ...Glossary...