Chapter 10 Appendix2-Insertion transducer
www.supmea.com
- 71 -
10.4.2. Pipe parameter entry shortcuts
For example, measuring the diameter of DN200, pipe outside diameter is 219mm,
pipe wall thickness is 6mm, pipe inner diameter is 207mm, measuring medium is
water, and material is carbon steel, no liner, can be operated as follows:
Step1. Pipe outside diameter
Press
keys to enter the window M11 and enter the pipe
outside diameter, and then press the
key to confirm.
(For insertion transducer, M11 menu need to be entered the pipe inner
diameter)
Step2. Pipe wall thickness
Press the
key to enter the window M12, and enter the pipe
wall thickness, and press the
key to confirm.
(The Wall Thickness needs to be 0.01mm for use with insertion sensors.)
Step3. Pipe Material
Press the
keys to enter the window M14, press the
key, press the
or
key to select Pipe Material, and press the Enter
key to confirm.
Step4. Transducers type
Press the
keys to enter the window M23, press the
or
0.
Car bon
Steel
[14
Pipe
Mater i
al
Pipe Outer Diameter
207 mm
Pipe Wall Thickness
0.01mm
Transducer Type [23
1.Plug- in TypeB45