MG, SG & AAA Series Boilers – User’s Information Manual 

 

 

 

4

LIGHTING INSTRUCTIONS FOR INTERMITTENT ELECTRONIC IGNITION 
WITH COMBINATION GAS VALVE. 

1.  This boiler is equipped with an ignition device 

which automatically lights the pilot.  Do not try 
to light the pilot by hand.  Ensure gas supply 
to the boiler is turned on. 

2.  STOP!  Read the safety instructions in  

Section 2

3.  Set the room thermostat to lowest setting. 
4.  Turn off all electrical power to the appliance. 
5.  Remove control access panel if necessary. 
6.  Push in gas control knob slightly and turn 

clockwise 

 to "OFF". 

 

NOTE: On some gas valves the knob cannot 
be turned to "OFF" or “ON” position unless 
knob is pushed in slightly.  Do not force. 

7.  Wait five (5) minutes to clear out any gas.  

Then smell for gas, including near the floor.  
If you smell gas, STOP! Follow "A" in the 
safety instructions in 

Section 2

.  If you don't 

smell gas, go to the next step. 

8.  Turn gas control knob counterclockwise 

 

to "ON". 

9. 

Replace control access panel if necessary. 

10.  Turn on all electrical power to the Boiler. 
11.  Set room thermostat to desired setting. 
12.  If the appliance will not operate, follow the 

instructions "To Turn Off Gas To Boiler" in 

Section 7

 and call your service technician or 

gas supplier. 

To turn off gas to boiler or emergency shut-off 

Follow 

Section 6

LIGHTING INSTRUCTIONS FOR INTERMITTENT ELECTRONIC IGNITION 

WITH NON-COMBINATION GAS VALVE. 

This boiler is equipped with an ignition device, which automatically lights the pilot.  Do not try to light the 
pilot by hand.  Before turning on the electrical power switch, be sure all gas supply lines are purged of air 
and power supply to control is the correct voltage. 

If the pilot or main burners are not lit or the control system is locked-out due to flame failure, close the 
main and pilot gas shut-off valves and call your service technician or gas supplier. If you smell gas, 
STOP! Follow “A” in the safety instructions in 

Section 2

Check Control Operation 

1. STOP! Read the safety instructions in 

Section 2

2.  For 100% shut off check, close main and pilot 

manual gas shut off valves, turn off all electric 
power to the boiler and wait for five minutes to 
clear out any gas. 

3.  Then smell for gas, including near the floor.  If 

you smell gas, STOP! Follow safety instructions 
in 

Section 2

.  If you don’t smell gas, go to the 

next step. 

4.  Set the thermostat above room temperature 

and turn on all electric power to the boiler to 
energize the electronic ignition and pilot valve.  
After a few seconds, the control system 
should “lockout” and all functions are off. 

5.  To take the control system out of “lockout” 

either press the reset button or interrupt power 
to the boiler, depending on the boiler 

controller.  Some controllers will retry ignition 
automatically after 5 minutes lockout. 

Start System 

1.  Turn on the main and pilot manual gas shut-

off valves. 

2.  Set thermostat above room temperature and 

turn on all electrical power to the boiler. 

3.  Once the pilot flame is proven, the controller 

opens the main burner gas valves.  The pilot 
flame will ignite the gas as it exits the main 
burner ports. 

4.  Set thermostat to the desired setting to put 

system back in service. 

Relight Operation 

Five minutes complete shut off period is required 
before attempting to relight the boiler.  To relight 
the boiler, follow the Start System procedure 
(above). 

To turn off gas to boiler or emergency shut-off 

Follow 

Section 6

Содержание AAA-3000-E

Страница 1: ...switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire depa...

Страница 2: ...the appliance and or equipment such that only one service switch services both the appliance and the carbon monoxide detector b Have battery back up power c Meet ANSI UL 2034 Standards and comply wit...

Страница 3: ...phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department B Use only your hand to push in or turn the gas control knob Never use tools If the knob wi...

Страница 4: ...purged of air and power supply to control is the correct voltage If the pilot or main burners are not lit or the control system is locked out due to flame failure close the main and pilot gas shut of...

Страница 5: ...a clear and free from combustible materials gasoline and other flammable vapors and liquids Do not store anything against the boiler or allow dirt or debris to accumulate in the area immediately surro...

Страница 6: ...as exhaust venting considerations must conform to the applicable codes If any alteration of the air supply and venting system is required contact a qualified service agency The boiler room must never...

Страница 7: ...iately contact a qualified service agency for adjustment or corrective measures 13 BOILER WATER Avoid unnecessary replenishment of system water It can allow oxygen to enter the system and cause seriou...

Страница 8: ...ef valve Avoid contact with the hot water or steam discharged to prevent personal injury 15 BLOCKED VENT AND FLAME ROLL OUT SAFETY SWITCHES Applicable to all boilers with an input rating less than 300...

Страница 9: ...rculating pumps used with hot water heating systems should be inspected for water leaks Check for weeping at pressure relief valve outlet during normal operation Listen for unusual audible sounds in t...

Страница 10: ...MG SG AAA Series Boilers User s Information Manual 10 18 TYPICAL RESIDENTIAL BOILER COMPONENT LOCATIONS...

Страница 11: ...MG SG AAA Series Boilers User s Information Manual 11 19 TYPICAL COMMERCIAL BOILER COMPONENT LOCATIONS...

Страница 12: ...Combination Gas Valve 4 6 To Turn off Gas to the Boiler or Emergency Shut Off 5 7 Area around Boiler 5 8 Check for Gas Leaks 5 9 Corrosive Atmospheres 6 10 Air Supply for Combustion and Ventilation 6...

Отзывы: