Figure 31.
Alarm Threshold Setup
External Alarm
The CrossFire system supports external alarms inputs that as UPS failure, condition of air, entrance guard, etc.
External Alarm of A2
The external alarms are input to a DB9 dry contact interface in the front panel of A2. See the details of the pin in Figure
32. The external alarms can be monitored as normally closed or normally open
Use the following steps to view and configure the external alarms.
1.
Log in the A2 OMT, and go to the Element
Alarms
section.
2.
Select the appropriate alarm level for external alarm in use at the bottom of the page.
3.
Click
Set
to save the settings.
4.
Go to the
External
Alarms
section
5.
Type
External alarm name
and select
Normally closed
or
Normally open
mode.
6.
Click
Set
to save the name.