background image

IS-ST-PM5C

Installation

The PM-5C must be installed in a location that exposes the 

moisture grid to a clear view of the sky and any precipitation. 

The unit should not be mounted directly under eaves, 

overhangs, or other obstructions that can block precipitation 

from reaching the moisture grid. 
Do not install the sensor close to the ground, or any other 

location, that can cause the sensor to be buried in snow. 
Mount the PM-5C outdoors, away from furnace vents, dryer 

vents, and other sources of heat. The PM-5C can be mounted 

to a free-standing conduit or by using the mounting holes in 

each corner of the enclosure. Do not drill holes in the enclosure.
Wire the controller in accordance to the provided schematics

Setting Configuration

Before turning power on to the PM-5C sensor, it is important to 

set all control modes and settings.
1.   Place the control in Standby/Reset with the switch mounted 

on the side before making configuration switch changes.  

Remember to return it to Automatic mode when finished.

2.   Set the Trigger Temperature by adjusting 

the TRIG TEMP control for desired melting 

conditions. Precipitation below this 

temperature is assumed to be snow, above 

this is rain.Control comes with the TRIG 

TEMP dial set to 39°F (4°C).

Snow & Ice Sensor Control

These instructions are intended to provide specific application 

information for installing the PM-5C snow and ice sensor control 

with the ProMelt snow melt products.
Please refer to the full instruction manual given with the product 

for further installation, Caution, and operation instruction. 
The PM-5C is a multi-voltage, self contained temperature, snow 

and ice sensor control. Each PM-5C can be set to operate 

with either 120, 208, 240, or 277 VAC and can provide up to 

60 amps of service to the load (2 circuits 30 amps each). The 

integrated snow sensor is heated to allow for snow, ice, or 

freezing rain to melt, allowing proper detection of environmental 

conditions.

4.   Determine how the sensor operates by setting the toggles 

located at S1.

Snow:

   The control will operate when 

precipitation is detected below the 

Temp Adjust setting. 

Recommended ON.

Rain:  

The control will operate when precipitation is detected 

above the Temp Adjust setting. Required OFF.

DEL:

 

 The control will operate with a Delay Off time. If this 

function is set to Off, the control will operate with a 

2 minute delay to prevent short-cycling of external 

components.  

Recommended ON.

LTC:

 

 The control will operate in Low Temperature 

Cutoff mode, preventing operation when Ambient 

Temperatures (AT) fall below 15°F (9.5°C). 

Recommended: ON (for systems with limited 

heat output).

LD:  

This Long Delay switch determines the time span of 

the Delay Off drying cycle. Either 30-90 minutes (LD 

Off) or 2-6 hours (LD On). 

Recommended OFF.

5.  Set the precipitation SENSITIVITY to reduce nuisance 

triggering. MORE to trigger immediately upon detection. 

LESS to trigger with up to 120 seconds of detection. 

Recommended MORE

 to begin, then adjust as needed.

Power must be cycled for switch changes to take effect.

PM-5C provides integrated air and moisture detection within a  

rainproof and ice-resistant enclosure.

2 x 30 A 277V AC, 20 A 28V DC

AVERTISSEMENT: IL PEUT Y AVOIR UN CIRCUIT SECONDAIRE SOUS TENSION

CERTIFIED TO CAN/CSA STD C22.2 NO. 14

CONFORMS TO UL STD 508

100-277V AC 0.15 A 50/60 Hz

ENCLOSURE TYPE 3R

RAIN/SNOW SENSOR CONTROLLER

WARNING: THIS UNIT MAY BE SUPPLIED BY MORE THAN ONE BREAKER

CONTROL

INPUT

US

C

Intertek

3175102

CONTROL SWITCH

STANDBY/RESET

MANUAL ON

AUTOMATIC

T

S

LI ED

ACTIVATED

ENGINEERING

DANGER

DS-5C

AUTOMATED

SYSTEMS

INDICATOR

POWER

OFF

CM

Air Temperature Sensor

Wiring Access

Control Switch

Moisture Grid

Instructions for Installing PM-5C

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use 

information can result in death,
serious personal injury, property damage, or damage 

to the equipment.
Keep this Manual for future reference.

!

 

WARNING

1.  

THIS UNIT SHOULD BE INSTALLED ONLY BY  

QUALIFIED PERSONNEL!

2.  To prevent the risk of electric shock, disconnect all 

power from the control and associated equipment 

before opening the front cover plate.

3.  Do not drill holes through the electrical enclosure for 

mounting.  

Mount the control to a free-standing conduit or via 

the pre-determined mounting holes.

4. Ensure front cover gasket is properly installed when 

    replacing cover.

DELAY OFF

TRIG TEMP

3.   Set the DELAY OFF time for 30 to 90 

minutes (LD Off) or 2 to 6 hours (LD On). 

The Delay function will allow the snow 

melt system to run for the set time frame 

after moisture is no longer detected 

(once snowfall has stopped). This is to 

help prevent "black ice" from forming. 