4. TROUBLESHOOTING 

 

 

Trouble Name 

Possible Cause 

Troubleshoot Suggestions 

AC over voltage 

AC  input  voltage  is 
higher than standard. 

1.  If instantaneous voltage is over 264Vac

wait for 

the power grid to recover normally. 

2.  Check and analyse background monitoring data. If 

the voltage in this area is over-voltage for a long 
time,  please  increase  the  input  over-voltage 
protection  value  by  the  configuration  software; 
max. value is up to 300Vac. 

3.  If  the  problem  cannot  be  eliminated,  please 

contact us.  

AC under voltage 

AC  input  voltage  is 
lower than standard. 

1.  If instantaneous voltage is under 140Vac, wait for 

the power grid to recover to normal. 

2.  Check and analyse background monitoring data. If 

the voltage in this area is under-voltage for a long 
time,  please  reduce  the  input  under-voltage 
protection  value  by  the  configuration  software; 
min. value is 140Vac. 

3.  If  the  problem  cannot  be  eliminated,  please 

contact us. 

AC over current 

AC  input  current  is 
higher than standard. 

1.  Immediately  disconnect  the  leakage/over-current 

protection circuit breaker of the distribution box. 

2.  Check  whether  there  is  low  impedance  or  short 

circuit between two lines of output line of AC EV 
charging station. 

3.  After the above problems are eliminated, power on 

again.  If  the  problem  still  cannot  be  eliminated, 
please contact us. 

AC over frequency 

AC  input  frequency  is 
higher than standard. 

1.  If instantaneous frequency exceeds 55Hz, wait for 

the power grid to recover to normal. 

2.  Check  the  input  voltage  frequency  in  the 

background monitoring data. If it is too high for a 
long  time,  please  contact  the  power  supply 
department for handling. 

AC under frequency 

AC  input  frequency  is 
lower than standard. 

1.  If the instantaneous frequency is less than 45Hz, 

wait for the power grid to recover to normal. 

2.  Check  the  input  voltage  frequency  in  the 

background monitoring data. If it is too lower for a 
long time, please reduce the protection frequency; 
value, min. value up to 40Hz. 

3.  If  the  problem  cannot  be  eliminated,  please 

contact us. 

Содержание SUN-7KW-EV2

Страница 1: ...ing Station SUN 7KW EV2 USER MANUAL Global Tech China Ltd 3 Floor Wai Yip Industrial Building 171 Wai Yip Street Kwun Tong Kowloon Hong Kong Tel 852 2884 4318 Fax 8522884 4816 www sunsynk com sales gl...

Страница 2: ...W 4 2 2 PRINCIPLE BLOCK DIAGRAM 4 2 3 KEY PARAMETERS 5 2 4 PRODUCT FEATURES 5 3 OPERATION INSTRUCTION 6 3 1 CHECKING AND DEBUGGING 6 3 2 POWER ON 6 3 3 OPERATION 6 3 3 1 CHARGING CONNECTION 6 3 3 2 ST...

Страница 3: ...y cloth It is strictly prohibited to touch the charging gun core with hands when it is electrified Do not attempt to dismantle repair modify the charging pile If there is any need for maintenance or m...

Страница 4: ...arging It is composed of a charging body wall hanging rear plate floor standing pole optional accessories etc It features charging protection card charging scan code charging mobile payment network mo...

Страница 5: ...ctions Over Under voltage protection over current protection short circuit protection ground protection lightning protection emergency stop protection leakage protection Functions Ethernet GPRS 4G Wif...

Страница 6: ...f the charging pile is reasonable 3 2 Power On a Confirm that the above inspection items meet the requirement b After the circuit breaker of the upper distribution box is closed open the upper cover o...

Страница 7: ...The user connects the charging gun correctly and uses the configured card to enter charging After the charging is finished please scan the card for payment first and then plug out the gun otherwise th...

Страница 8: ...he charge and deliver the charging data including charging time charging amount charging cost to the owner s APP or the bound WeChat public number The owner can also view the historical consumption re...

Страница 9: ...m cannot be eliminated please contact us AC over current AC input current is higher than standard 1 Immediately disconnect the leakage over current protection circuit breaker of the distribution box 2...

Страница 10: ...Input output poor grounding or input L N reverse connection 1 Disconnect the distribution box leakage over current protection switch immediately 2 Check whether the AC pile input output line is groun...