Website: www.sunsynk.com E-mail: [email protected]
32
4.12. Battery Discharge Page
To configure inverter shutdown
settings click on the “Battery” icon and then on “Shut Down”.
The voltage displayed on the Sunsynk Parity Inverter will vary depending on whether the inverter is
charging or discharging the batteries.
NOTE
Shutdown causes the inverter to enter standby mode. It will not completely shut down the inverter.
The total shutdown is below 19V.
What this page displays:
Inverter shut down the voltage as a voltage
or % .
Inverter low battery warning voltage or %.
Restart voltage as a voltage or %.
What you can do from this page:
Adjust battery shut down (voltage or %)
Adjust low battery warning (voltage or %)
Adjust restart (voltage or %)
Since the batteries are 48V the figure on the
left is x4:
Fully Charged 50.54V (Discharge Mode)
Fully Charged 58.50V (Charge Mode)
75% Charged 49.60V (Discharge Mode)
75% Charged 54.80V (Charge Mode)
25% Charged 48.00V (Discharge Mode)
25% Charged 50.80V (Charge Mode)
Completely Discharged 47.50V
Setting the cut-off higher is better for the
batteries.