7 Parameters of LCD
Operation Manual
30
Parameter
Description
Power-off saved (Pf)
If the power factor setting can be saved when the LCD screen is
powered off
Power-off saved (P-limited)
If the limit power(%) setting can be saved when the LCD screen is
powered off
SVG switch
If the reactive power compensation is activated or deactivated
T-recover (s)
Automatic recovery time when fault occurs
Setting ranges and default values of the running parameters are described in the following
table.
Parameter
Range
Default
Vmppt-max (V)*
460~850
850
Vmppt-min (V)*
460~850
460
T-start-wait (s)
0~600
60
T-stop-delay (s)
0~600
0
stop slope (%/s)
0.1~100
100
P-rise rate (%/s)
0.01~10
10
P-decline rate (%/s)
0.01~10
10
Limit Power (%)
0~110
110
Pf -0.9~-1/0.9~1
1
Q-limit (%)
-100~100
0
Q-adjust switch
Close/Pf/Q-limit
Pf can be adjusted
Power-off saved (Pf)
Save/Not Save
Save
Power-off saved (P-limited)
Save/Not Save
Not Save
SVG switch**
Enable/Disable
Disable
T-recover (s)
20~600
60
Note: * non-settable
** at night when the inverter enters standby mode (but not enters the deep standby mode with
lower power consumption), the SVG function needs to be activated: first stop the inverter by the
LCD button and then start; set the SVG switch to “Enable”. The SVG is an optional function for this
inverter.
Improper parameter configuration may affect the normal operation of the inverter!
Only authorized personnel can configure these parameters.
Should any question or doubt occurs, please contact Sungrow.
Please refer to the LCD screen for the specific setting ranges of these parameters.
7.3
Protection Parameter
7.3.1
Setting Protection Parameter
Step 1
Tap “Function” from the default menu;
Step 2
Tap “Set-parameter”;
Step 3
Tap “Pro-parameter” after entering the correct password.