User Manual
45
PC
Shielding layer is grounded
120
Ω
Inverter 1
RS485-2
Inverter 2
Inverter n
Multiple inverters in daisy chain
120
Ω
RS485-2
RS485-2
Data Logger
Ethernet
terminal
RS485
terminal
Ethernet port
RS485 cable
Ethernet cable
Inverter
Communication connection
(RS485 bus connection)
Terminating Resistor
n
≤
15
n>15
Inverter 1
Only out
No
120ohm
Yes
120ohm
Inverter
2~n-1
In and Out
A B GND
No
120ohm
Inverter n
In and Out
A B GND
No
120ohm
Yes
120ohm
6.5.3 RS485 Communication Connection
RS485A/B Bus Connection
Step 1
Lead the RS485 shielded twisted pair cables through the communication
cable gland to the configuration circuit board.
Step 2
Trip off the insulating layer of the communication cables for approximately 7
mm. Connect the cables to the RS485 bus terminal blocks.
Содержание SG36KTL-M