There are four communication terminals COM1, COM2,COM3 and COM4 on
the bottom of the inverter. Select the communication terminal according to
onsite conditions.
Disconnector (≥800V) and fuse (16A, gM) should be installed between the
inverter and the tracking system control cabinet.
Length of the cable connecting the internal wiring terminal of the inverter and
the fuse should be less than 2.5m.
5.9
RS485 Communication
5.9.1 Interface Description
The following figure shows the position of the communication wiring board in the
inverter as well as the terminals equipped for the wiring board.
The inverter is equipped with two groups of RS485 communication interfaces for
external communication connection.