Step 8
Secure the wires to corresponding terminals.
Note the terminal positions of PE wire and N wire. If a phase wire is connected
to the PE terminal or N terminal, unrecoverable damage may be caused to the
inverter.
Ensure that the depth L of the socket used is not less than 28mm.
Step 9
Gently pull the cable backwards to ensure firm connection, and fasten the swivel nut
clockwise.