68
P
Pa
arra
am
me
ette
err
D
De
effiin
niittiio
on
n//S
Se
ettttiin
ng
g
D
De
essc
crriip
pttiio
on
n
R
Ra
an
ng
ge
e
QP_EnableMode
Unconditional activation/
deactivation of Q(P) function
Yes/No
Q(U)Curve
Select the corresponding
curve according to local
regulations
Curve A/Curve B/Curve C*
QU_V1
Pre-set grid voltage U1 that
is reactive according to the
grid voltage
80.0%~100.0%
QU_Q1
Pre-set proportion of reactive
power according to the grid
voltage U1
[-60.0%~0]* Overload
Rate/1000
QU_V2
Pre-set grid voltage U2 that
is reactive according to the
grid voltage.
80.0%~100.0%
QU_Q2
Pre-set proportion of reactive
power according to the grid
voltage U2.
[-60.0%~60.0%]* Overload
Rate/1000
QU_V3
Pre-set grid voltage U3 that
is reactive according to the
grid voltage.
100.0%~120.0%
QU_Q3
Pre-set proportion of reactive
power according to the grid
voltage U3.
[-60.0%~60.0%]* Overload
Rate/1000
QU_V4
Pre-set grid voltage U4 that
is reactive according to the
grid voltage.
100.0%~120.0%
QU_Q4
Pre-set proportion of reactive
power according to the grid
voltage U4.
[0~60.0%]* Overload Rate/
1000
QU_EnterPower
Active power for Q(U)
function activation
20.0%~100.0%
QU_EXitPower
Active power for Q(U)
function deactivation
1.0%~20.0%
User Manual
Содержание SG125HX
Страница 1: ...User Manual PV Grid Connected Inverter SG125HX SG125HX UEN Ver14 202105 WWW SUNGROWPOWER COM...
Страница 2: ......
Страница 6: ......
Страница 10: ......
Страница 32: ...22 E En nd d 4 Mechanical Mounting User Manual...
Страница 45: ...35 Ensure that the depth L of the socket used is not less than 28mm User Manual 5 Electrical Connection...