45
5.10.3 Connection Procedure(Terminal Block)
RS485 communication cables should be shielded twisted pair cables or
shielded twisted pair Ethernet cables.
There are three communication terminals, and the silkscreen marks are
COM1/COM2/COM3. Please choose according to the actual situation.
step 1
Remove the communication junction box, see
.
step 2
Strip the protection layer and insulation layer by appropriate length.
step 3
Loosen the swivel nut of the junction box and select an appropriate seal according to
cable outer diameter. Lead the cable through the swivel nut, seal, and junction box
successively.
O
Ou
utte
err D
Diia
am
me
ette
err D
D((m
mm
m))
S
Se
ea
all
4.5~6
c
6~12
a+b
12~18
b
step 4
Secure the cable to the terminal base.
User Manual