29
5.5
Additional Grounding Connection
•
Since the inverter is transformerless, neither the negative pole nor the
positive pole of the PV string must be grounded. Otherwise, the inverter will
not operate normally.
•
Connect the additional grounding terminal to the protective grounding point
before AC cable connection, PV cable connection, and communication cable
connection.
•
The ground connection of this additional grounding terminal cannot replace
the connection of the PE terminal of the AC cable. Make sure those terminals
are both grounded reliably. SUNGROW shall not be held liable for any
damage caused by the violation.
5.5.1 Additional Grounding Requirements
All non-current carrying metal parts and device enclosures in the PV power system
should be grounded, for example, mounts of PV modules and the inverter enclosure.
When there is only one inverter in the PV system, connect the additional grounding
cable to a nearby grounding point.
When there are multiple inverters in the PV system, connect grounding points of all
inverters and the PV array frames to the equipotential cable (according to the onsite
conditions) to implement an equipotential connection.
5.5.2 Connection Procedure
step 1
Prepare the cable and OT/DT terminal,refer to
step 2
Remove the screw on the grounding terminal and fasten the cable with a screwdriver.
step 3
Apply paint to the grounding terminal to ensure corrosion resistance.
User Manual
Содержание SG125HX
Страница 1: ...User Manual PV Grid Connected Inverter SG125HX SG125HX UEN Ver14 202105 WWW SUNGROWPOWER COM...
Страница 2: ......
Страница 6: ......
Страница 10: ......
Страница 32: ...22 E En nd d 4 Mechanical Mounting User Manual...
Страница 45: ...35 Ensure that the depth L of the socket used is not less than 28mm User Manual 5 Electrical Connection...