User Manual
100
Fig. 10-20
Protection parameter
For convenient protection parameter setting, the protection parameters are
preset for certain countries. After country setting, select the protection stage as
single or multiple and then set the corresponding protection parameter.
Tab. 10-7
Single-stage Protection Parameters Explanation
Parameter
Range
Default
AC under-voltage single-stage protection value
60V-600V
528V
AC over-voltage single-stage protection value
477V-826V
660V
AC under-frequency single-stage protection
value
53.00Hz
-59.90Hz
59.80Hz
AC over-frequency single-stage protection value 65.00Hz
-62.00Hz
60.50Hz
Tab. 10-8
Multi-stage Protection Parameters Explanation
Parameter
Range
Default
AC under-voltage level 1 protection value
60V-600V
528V
AC over-voltage level 1 protection value
477V-826V
660V
AC under-frequency level 1 protection value 53.00Hz -59.90Hz
59.80Hz
AC over-frequency level 1 protection value
65.00Hz -62.00Hz
60.50Hz
AC under-voltage level 1 protection time
0s-600s
2s
AC over-voltage level 1 protection time
0s-600s
1s
AC under-frequency level 1 protection time
0s-600s
0.16s
AC over-frequency level 1 protection time
0s-600s
0.16s
AC under-voltage level 2 protection value
60V-600V
300V
AC over-voltage level 2 protection value
477V-826V
720V
Содержание SG125HV
Страница 1: ...SG125HV V1 UEN Ver10 201809 Version 1 0 User Manual SG125HV SG125HV 20 PV Grid connected Inverter...
Страница 2: ......
Страница 11: ...IX 11 4 Contact Information 109...
Страница 12: ......
Страница 24: ...1 Safety Instructions User Manual 12 service d utilisateur avant l utilisation...