5.7.3 Installing the PV Connector
step 1 Ensure that the DC switch is in "OFF" position. Otherwise, manually turn it to "OFF".
step 2 Check the cable connection of the PV string for polarity correctness and ensure that the
open circuit voltage in any case does not exceed the inverter input limit of 1,100 V.
step 3 Connect the PV connectors to corresponding terminals until there is an audible click.
step 4 Follow the foregoing steps to connect PV connectors of other PV strings.
step 5 Seal any unused PV terminal with a terminal cap.
- - End
5.8
Wiring of Tracking System Power Cable (optional)
step 1 Please refer to step 1 and step 2 in
5.6.3 Connection Procedure (For a multi-core cable)
step 2 Cut off the excess part of sealing ring according to cable diameter.