step 2 Assemble the cable ends with the crimping pliers.
1: Positive crimp contact
2
:
Negative crimp contact
step 3 For some countries such as Australia where the DC protection cover delivered separately
need to be installed on site, please firstly lead the PV cables through the waterproof terminal
on the DC protection cover before assembling the connector. See the guidance with the DC
protection cover for details.
PV cables with connectors cannot go through the waterproof terminal on the DC
protection cover. Rework may cause damage to the connectors, which will not be
covered by the warranty.
step 4 Lead the cable through cable gland, and insert the crimp contact into the insulator until it
snaps into place. Gently pull the cable backward to ensure firm connection. Tighten the ca-
ble gland and the insulator (torque 2.5 N.m to 3 N.m).
step 5 Check for polarity correctness.