93
Fault code
Fault name
Corrective measures
8
Grid Overfrequency
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly:
1. Measure the actual grid frequency, and con-
tact the local electric power company for solu-
tions if the grid frequency is beyond the set
range.
2. Check whether the protection parameters
are appropriately set via the App or the LCD.
3. Contact Sungrow Customer Service if the
preceding causes are ruled out and the fault
persists.
9
Grid Underfrequency
10
Grid Power Outage
Generally, the inverter will be reconnected to
the grid after the grid returns to normal. If the
fault occurs repeatedly:
1. Check whether the grid supplies power
reliably.
2. Check whether the AC cable is firmly in
place.
3. Check whether the AC cable is connected
to the correct terminal (whether the live wire
and the N wire are correctly in place).
4. Check whether the AC circuit breaker is
connected.
5. Contact Sungrow Customer Service if the
preceding causes are ruled out and the fault
persists.
12
Excess Leakage
Current
1. The fault can be caused by poor sunlight or
damp environment, and generally the inverter
will be reconnected to the grid after the envi-
ronment is improved.
2. If the environment is normal, check whether
the AC and DC cables are well insulated.
3. Contact Sungrow Customer Service if the
preceding causes are ruled out and the fault
persists.