A P P E N D I X
B
Requirements for Sun Rack 900
Cabinets
The table below lists the specifications of the Sun Rack 900 cabinet and the operating
location that are applicable to the rack installation requirements of the Sun Fire V890
server. You need one Sun Fire V890 server rackmounting kit for each Sun Fire V890
server that you will install into the Sun Rack 900 cabinet.
Cabinet Feature
Requirement
Load-Bearing Capacity
The Sun Rack 900 cabinet firmly supports the weight of two Sun
Fire V890 servers and the mounting hardware (up to 700 lb,
317.6 kg, depending on the server configuration).
Anti-Tilt Protection
The Sun Rack 900 cabinet provides several anti-tilt features,
including a sturdy anti-tip bar that prevents the cabinet from
moving or tilting forward when one or more systems or devices
are fully extended from the front of the cabinet.
Vertical Space
The Sun Rack 900 cabinet provides 38 rack units of vertical
space. Each Sun Fire V890 server requires 17 rack units (29.75
inches, 75.6 cm) of vertical space for cabinet installation.
Minimum Service
Access
An area not less than 3 feet (91 cm) deep must be
available in back of the cabinet for server installation and
service access.
An area not less than 48 inches (122 cm) deep must be
available in front of the cabinet for server installation and
server access.
An area not less than 36 inches (91 cm) wide must be
available on each side of the server when the server is
fully extended on the tray assembly.
When fully extended on the tray assembly, the server will
protrude 32.9 inches (83.6 cm) forward of the cabinet’s front
vertical mounting rails.
Содержание Sun Fire V890
Страница 9: ...Preface ix...
Страница 10: ...x Sun Fire V890 Server Rackmounting Guide May 2004...
Страница 44: ...34 Sun Fire V890 Server Rackmounting Guide May 2004...
Страница 70: ...60 Sun Fire V880 Server Rackmounting Guide May 2004...
Страница 102: ...92 Sun Fire V890 Server Rackmounting Guide May 2004...