Sun StorEdge™ L25 Tape Library and Sun StorEdge™ L100 Tape Library Installation Guide
Document 6423015-01, Ver. 1, Rel. 0
June 2002
Site Requirements
5
Figure 2 Vent Locations,
L100
Environmental
Requirements
0
The installation site (desktop or deskside library) or the interior of the
rack (rack mount library) must meet the following environmental
requirements:
• Humidity: 20% to 80%, non-condensing
• Temperature: 50°F to 104°F (10°C to 40°C)
• Altitude: -100 to +10,000 feet (-30 to +3,000 meters)
Power and
Grounding
0
The L25 and L100 power supplies accept 88 VAC to 264 VAC input
power at 47 Hz to 63 Hz.
The library must be connected to a grounded power outlet. If the
library is mounted in a rack, the rack must also be grounded.
Vents