92
Sun Datacenter Switch 3456 Installation Guide • December 2008
5. Enable both IPMB buses for all fabric cards and line cards, type:
The
enableAllIPMB
script runs the
enableipmb
command for both the A and B
buses for each fabric card and line card.
6. Enable standby power for all fabric cards and line cards, type:
The
enableAllStby
script runs the
enablestby
command for each fabric card
and line card.
7. Bring each fabric card to full power, type:
where
slot
is
0
to
17
.
8. Check fan operation, type:
If a fan’s speed is too low or the fan has stopped, investigate why. See the
Sun
Datacenter Switch 3456 Service Manual
for further assistance.
9. Bring each line card to full power, type:
where
slot
is
0
to
23
.
10. Again verify all installed components are recognized as installed, type:
If an installed component is not recognized, investigate why. See the
Sun
Datacenter Switch 3456 Administration Guide
and
Sun Datacenter Switch 3456 Service
Manual
for further assistance.
The Sun Datacenter Switch 3456 is now operational.
See the
Sun Datacenter Switch 3456 Administration Guide
for information about
administrative commands.
#
enableAllIPMB
#
enableAllStby
#
activate fc
slot
#
checkfans
#
activate lc
slot
#
showpresent
Содержание Datacenter Switch 3456
Страница 10: ...x Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Страница 14: ...xiv Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Страница 20: ...6 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Страница 48: ...34 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Страница 49: ...Chapter 5 Unpacking the Chassis 35 ...
Страница 73: ...58 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Страница 87: ...72 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Страница 97: ...82 Sun Datacenter Switch 3456 Installation Guide December 2008 ...
Страница 125: ...110 Sun Datacenter Switch 3456 Installation Guide December 2008 ...