5.4. Changing Parameters
P2 01 P2 01 P2 01 P2 01 P2 01
Stop
P1-01
P1-08
30.0A
P1-08
Stop
15kW 400V 3Ph 50.0Hz
30.0A
P1-08
30.0
3.0 30.0A
15kW 400V 3Ph
Press and hold the
Navigate key > 2
seconds.
Use the up and down
keys to select the
required parameter.
Drives with TFT
display will show the
present parameter
value on the lower
line of the display.
Press the Navigate
key for < 1 second.
Adjust the value using
the Up and Down keys.
Drives with TFT
display will show
the maximum and
minimum possible
settings on the lower
line of the display.
Press for < 1 second
to return to the
parameter menu.
Press for > 2 seconds
to return to the
operating display.
5.5. Parameter Factory Reset / User Reset
Optidrive P2 provides a feature to allow the user to define their own default parameter set. After commissioning all required
parameters, the user can save these as the default parameters by setting P6-29 = 1. If required, the User Default Parameters may be
cleared by setting P6-29 = 2.
If the user wishes to reload the User Default Parameters from the drive memory, the following procedure is used.
Factory Parameter Reset :
User Parameter Reset :
P2 01 P2 01
P2 01
P2 01 P2 01 P2 01
Stop
P-Def
Stop
Stop
U-Def
Stop
15kW 400V 3Ph 50.0Hz
15kW 400V 3Ph
P1-08
30.0
3.0 30.0A
15kW 400V 3Ph
Press and hold the Up,
Down, Start and Stop
keys for >2s.
The display shows
P-Def. Briefly press the
Stop key.
The display returns to
Stop. All parameters
are reset to Factory
defaults.
Press and hold the Up,
Down and Stop keys
for >2s.
The display shows
U-Def. Briefly press
the Stop key.
The display returns to
Stop. All parameters
are reset to Factory
defaults.
5.6. Resetting the Drive Following a Trip
Optidrive P2 has many protection features, designed to protect both the drive and motor from accidental damage. When any of these
protection features are activated, the drive will trip, and display a fault message. The fault messages are listed in section
When a trip occurs, after the cause of the trip has been investigated and rectified, the user can reset the trip in one of the following ways:
Press the keypad Stop key.
Power off the drive completely, then power on again.
If P1-13 > 0, switch off digital input 1, then back on again.
If P1-12 = 4, reset via the fieldbus interface.
If P1-12 = 6, reset via CAN.