Quick Basic Installation Guide CP 116 & CP 216 

 

Key board 

 

To leave the main picture and enter the menus; push 

Down Arrow

 

 

Use 

Up

 & 

Down Arrow

 to step between submenus and confirm with 

Enter

 

 

Change value with 

Enter

 at chosen function, give the password and change value with 

Up/Down  

 

Go back in the menus by 

Left

 and to main picture by 

Esc 

 
Password

 

There are three security levels: 

1.  Daily operations, such as acknowledging an alarm or stopping a pump, do not require any pass code or authorization. 
2.  Operational settings, such as settings for the start or stop levels for the pump, require a pass code at the level of 

Operator

3.  Configuration settings that affect the basic functionality or access, such as the type of level sensor, require a pass code at the level of 

System

The factory default pass codes are 

1

 and 

2

 respectively, but the codes can be changed under the menu item 

Settings – System – Change Passcode

 

After Installation and power up first time 

Start to do a 

Factory Default

 

Reset

 by holding down both 

Right/Left arrows

 for 10 seconds. The cabinet will when restart with the factory default settings. 

Check the firmware by 

[Down Arrow] – Show Status – System

. Update the firmware if necessary. Find latest firmware at C&M ftp-site. Be aware that CP 116 

and CP 216 do 

not

 have same firmware. The built-in sensor has fixed range 0 – 3.5 meters. 

 

 

Basic settings 

1. 

Set the Language 

 

[Down Arrow] – Settings – Language 

2. 

Are you using Level Sensor or built-in Air Pressure tube? 

 

[Down Arrow] – Settings – Analoge Inputs 

3. 

Set the Start / Stop levels 

 

[Down Arrow] – Settings – Pump X – Start and Stop levels 

4. 

Station flow 

 

[Down Arrow] – Settings – Pump pit – Station Flow – Pit area 

5. 

The pumps use to be marked with the “Nominal Current”; that 
value shall be typed into 

[Down Arrow] – Settings – Pump x – Pump 

parameters. 

This is the place to activate the temperature and leakage 

sensors as well.

 

6. 

Look at the main picture and start one pump manually, notice the 

current consuming in the display. The nominal value is higher than 
what you just read. The alarm for high current shall be set in the 
middle of those two values and be typed in at 

Settings – Pump X – 

Pump Alarms – High Motor current

 

 

7. 

If Low Level Float is used; go into the menus and change in 

Settings – Digital Inputs – Digital in 4

 to 

NC

 (Normally Closed) 

 
 
 