![Sulzer Metco ECO ARC 600 Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/sulzer-metco/eco-arc-600/eco-arc-600_manual_1390515041.webp)
ECO ARC 600
3-3
Revision 1/10/08
3.2
Energy supply
Caution!
Work on electrical systems and equipment should only be performed
by a qualified electrician.
3.2.1 Electrical supply
Note
•
Making currents from major loads and other mains fluctuations
interrupt spraying.
•
400 V mains voltage should only be under-/ overshot by a maxi-
mum of 5%.
4 - wire mains connection
3 Phases
1 Earth
black, brown, grey
yellow-green
Mains voltage
400 V, 50 - 60 Hz
Nominal current
< 38 A
Fuse
50 A
Cable extension
Dimensions (for Cu)
(No. of leads x lead-profile in mm²)
up to 20 m
5 x 6
up to 50 m
5 x 10
up to 100 m
5 x 16
Содержание ECO ARC 600
Страница 6: ......
Страница 47: ...ECO ARC 600 5 1 Revision 1 10 08...
Страница 74: ...ECO ARC 600 7 6 Revision 1 10 08...
Страница 75: ...ECO ARC 600 8 1 Revision 1 10 08...
Страница 88: ...ECO ARC 600 8 14 Revision 1 10 08 T2 K1 A10 F4 D10 F2 1 F2 2 F3 K3 F21 F22 F23...
Страница 94: ...ECO ARC 600 9 2 Revision 1 10 08 9 2 Circuit diagram...