PosNo
Description
Quantity
Type
1a, 1b
Mounting angles, can be mounted
either to the left or the right side of
the case
2
-
2
Screw
8
M4x6
3
Washer
8
M4x6
17.4.3
Wall mounting
IP10316-1 v1
17.4.3.1
Overview
M11973-3 v6
The IED can be mounted on a wall, a panel or in a cubicle.
Use only the screws included in the mounting kit when mounting
the plates and the angles on the IED. Screws with wrong dimension
may damage the PCBs inside the IED.
If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for any communication
modules with fiber connection.
1MRK 505 384-UEN A
Section 17
IED hardware
Breaker protection REQ650 2.2 IEC
719
Technical manual