The outputs from the above configured SMAI block shall only be
used for Overfrequency protection (SAPTOF), Underfrequency
protection (SAPTUF) and Rate-of-change frequency protection
(SAPFRC) due to that all other information except frequency and
positive sequence voltage might be wrongly calculated.
16.9
Summation block 3 phase 3PHSUM
SEMOD55968-1 v2
16.9.1
Functionality
SEMOD55976-4 v4
Summation block 3 phase function 3PHSUM is used to get the sum of two sets of
three-phase analog signals (of the same type) for those IED functions that might
need it.
16.9.2
Function block
SEMOD54885-4 v3
3PHSUM
BLOCK
REVROT
^G1AI3P*
^G2AI3P*
AI3P
AI1
AI2
AI3
AI4
IEC05000441-3-en.vsdx
IEC05000441 V3 EN-US
Figure 303:
3PHSUM function block
16.9.3
Signals
SEMOD55989-1 v2
PID-6428-INPUTSIGNALS v3
Table 532:
3PHSUM Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block
BLKGR1
BOOLEAN
0
Block input for group 1
BLKGR2
BOOLEAN
0
Block input for group 2
REVROT
BOOLEAN
0
Reverse rotation
G1AI3P
GROUP
SIGNAL
-
Group 1 three phase analog input from first SMAI
G2AI3P
GROUP
SIGNAL
-
Group 2 three phase analog input from second
SMAI
1MRK 505 384-UEN A
Section 16
Basic IED functions
Breaker protection REQ650 2.2 IEC
673
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...