14.8.13.3
Function block
GUID-6EC8453E-0D00-4720-95A6-156C41CA46BB v1
IEC10000285-1-en.vsd
I103GENCMD
BLOCK
^CMD_OFF
^CMD_ON
IEC10000285 V1 EN-US
Figure 282:
I103GENCMD function block
14.8.13.4
Signals
PID-3970-INPUTSIGNALS v5
Table 461:
I103GENCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of command
PID-3970-OUTPUTSIGNALS v5
Table 462:
I103GENCMD Output signals
Name
Type
Description
CMD_OFF
BOOLEAN
Command output OFF
CMD_ON
BOOLEAN
Command output ON
14.8.13.5
Settings
PID-3970-SETTINGS v5
Table 463:
I103GENCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
PulseLength
0.000 - 60.000
s
0.001
0.400
Pulse length
InfNo
1 - 255
-
1
1
Information number for command output
(1-255)
14.8.14
IED commands with position and select for IEC
60870-5-103 I103POSCMD
14.8.14.1
Functionality
GUID-1E40B94D-B6A6-42F0-8757-A47B8A3FA3CD v7
I103POSCMD is a transceiver function that monitors activity on its input signals
and interprets any state transition into commands then sent over an established IEC
60870-5-103 link. Additionally, it listens for general interrogation (GI) requests
and replies to those with a GI response message with the current state of each
connected input.
Section 14
1MRK 505 384-UEN A
Station communication
606
Breaker protection REQ650 2.2 IEC
Technical manual
Содержание impreza 2017
Страница 1: ...RELION 650 SERIES Breaker protection REQ650 Version 2 2 Technical manual...
Страница 2: ......
Страница 32: ...26...
Страница 42: ...36...
Страница 50: ...44...
Страница 168: ...162...
Страница 226: ...220...
Страница 396: ...390...
Страница 498: ...492...
Страница 512: ...506...
Страница 528: ...522...
Страница 632: ...626...
Страница 650: ...644...
Страница 738: ...732...
Страница 784: ...778...
Страница 785: ...779...