16
EN/06.2016/i01 © STULZ S.p.A. – all rights reserved
WPA ExPlOrEr OrIGINAl INSTrUCTIONS
3.2 Storage
If you put the unit into intermediate storage before the installation, the following measures have
to be carried out to protect the unit from damage and corrosion:
• Make sure that the water connections are provided with protective hoods. If the intermediate
storage exceeds 2 months, we recommend filling the pipes with nitrogen.
• The temperature at the storage point should not be higher than 45°C and not lower than
–20°C, and the site should not be exposed to direct sunlight.
• The unit should be packaged before the storage to avoid the risk of damage and corrosion
especially of the heat exchanger fins.
• The unit should be stored in a location with minimum activity to reduce the risk of accidental
physical damage.
• A periodic inspection is highly recommended. If your chiller contains refrigerant gas during the
storage period you also have to consider the current F-Gas regulations and EN 378.
3.3 Transport
The STULZ chillers can be lifted and moved by lifting devices with ropes or belts. For this pur-
pose there are openings in the base frame, through which steel tubes must be pushed. The steel
tubes are supplied and already inserted in the chiller. The steel bars are provided with a latch on
both ends to prevent the ropes from protruding.
The drawings on the following pages show the dimensions for the suspension points and the
position of the centre.
INFOrMATION
The rope forces are higher than the weight forces according to the geometry. Due to the risk
of scratching the side planking we advise not to use chains.
3.3.1 Transport protection
The standard packaging of the chiller is bubble wrap around the chiller and at the top.
WArNING
The standard packaging is not suitable for transport by sea or by air