background image

Chapter 1: Hardware

1-5

Stride MQTT Gateway User Manual, 1st Edition

Environmental Specifications

Operating Temperature

0°C to +60°C [32°F to +140°F]

Storage Temperature

−20°C to +70°C [−4°F to +158°F]

Humidity

0–90%, noncondensing

Maximum Altitude

2000m

IP Rating

IP20

Installation

Indoor

Category of Installation

II

Pollution Degree

2

EMC

Immunity
Emission

EN61000-6-2
EN61000-6-4

Agency Approvals

CE, FCC, RoHS

Dimensional Drawings 

  91.0

3.58

 

  71.5

2.81

 

RESET

BUTTON

  44.9

1.77

 

  46.1

1.81

 

  62.5

2.46

 

  62.5

2.46

 

5-WIRE

CONNECTOR

Units: mm [in]

ETHERNET 

PORT

RoHS Compliant

RoHS

Содержание MQTT

Страница 1: ...apter Chapter 1 1 1 In This Chapter Hardware Overview 2 2 Specifications 2 3 Dimensional Drawings 2 4 Installation 2 5 Mounting 2 5 Wiring 2 6 Operation 2 7 Front Panel Indicators 2 8 Recovery Mode 2...

Страница 2: ...roup will work with you to answer your questions They are available Monday through Friday from 9 00 a m to 6 00 p m Eastern Time We also encourage you to visit our web site where you can find technica...

Страница 3: ...structure can be configured to better adapt to different MQTT brokers e g Amazon AWS IBM Watson IoT Mosquitto etc It is possible to remotely update the firmware through the web interface The gateway h...

Страница 4: ...us Ethernet Connections 8 WiFi Specifications Model SGW MQ1611 WF Only WiFi Standards 802 11 a b g n ac Frequency Bands 2400MHz 5500MHz Antenna Internal Network Ports Web User Interface 80 Modbus 502...

Страница 5: ...4 F to 158 F Humidity 0 90 noncondensing Maximum Altitude 2000m IP Rating IP20 Installation Indoor Category of Installation II Pollution Degree 2 EMC Immunity Emission EN61000 6 2 EN61000 6 4 Agency A...

Страница 6: ...e gateway Avoid placing raceways or other objects where airflow could be obstructed Avoid mounting the gateway above equipment that generates heat ideally locate the gateway in the lower part of the p...

Страница 7: ...to improve our products and services so we reserve the right to make changes to the products and or publications at any time without notice and without obligation This publication may also discuss fe...

Страница 8: ...ion to MQTT broker and one or more Modbus TCP or Modbus RTU over TCP servers USB x2 Future Use Terminal Connector Wiring Specifications Wire Size 0 8 2 1 mm2 14 18 AWG Torque 0 5 N m Stripping Length...

Страница 9: ...Front Panel Indicators The Stride MQTT Gateway has four status LEDs as shown below Front Panel LEDs LED Color State Description PWR GREEN ON Device powered OFF Device unpowered ERR YELLOW OFF No erro...

Страница 10: ...rmware updates To enter Recovery Mode press and hold the recessed reset button on the front of the gateway while applying power Continue to hold the reset button until the ERR light stops blinking abo...

Отзывы: