MAXIMUM BOILER TEMPERATURE
MINIMUM BOILER TEMPERATURE
°
C
°
C
90
70
90
70
FLUE TEMPERATURE MAXIMUM OUTPUT
°
C
135
140
FLUE TEMPERATURE MINIMUM OUTPUT
°
C
95
95
FLUE EXHAUST GAS FLOW RATE MAX OUTPUT
Kg/Sec
0.0176
0.0280
FLUE EXHAUST GAS FLOW RATE MIN OUTPUT
Kg/Sec
0.0079
0.0140
EFFICIENCY
%
91
85
BOILER WATER CONTENT
LTR
74
118
HYDRAULIC RESISTANCE DELTA T 10 C
mbar
7
7
NOMINAL OUTPUT
KW
25
40
MINIMUM OUTPUT
KW
8
13
HYDRAULIC RESISTANCE DELTA T 20 C
mbar
2
2
BOILER WEIGHT
Kg
340
459
BOILER CLASS EN303-5
3
3
MAXIMUM OPERATING PRESSURE
BAR
2.5
2.5
MAXIMUM TEST PRESSURE
BAR
5
5
MAXIMUM CHIMNEY (DRAUGHT) NEGATIVE
PRESSURE
PA
ii
12
15
FLOW & RETURN CONNECTION SIZE
INCH
1
1
¼
FLUE CONNECTION DIAMETER
m m
i
130 i
130 i
MAXIMUM CAPACITY OF THE STANDARD PELLET
HOPPER
Kg
120
170
ELECTRICAL SUPPLY/AMPERAGE
230V 50HZ
MAX 1 AMP
230V 50HZ
MAX 1 AMP
WATTAGE DURING NORMAL OPERATION
W
100
123
WATTAGE DURING IGNITION PHASE
W
300
323
Biotec 25
Biotec 40
Data subject to change without notice.
TECHNICAL DATA
i. It will be necessary to fit an adapter in the Flue pipe connection to increase the Flue diameter to the required
minimum Flue diameter of 150 mm (as previously stipulated) to comply with U.K. regulations
ii A Draught stabiliser (by others) should be fitted to the flue to maintain the required flue draught.
STREBEL recommends pellets with a diameter of 6 to 8 mm and length of 10 to 30 mm to
DIN ENplus A1 as referred to in EN 14961-2 A1