Unpacking STRATUS
Air Conditioning Equipment
Always keep air conditioner unit top up as shown by the
packaging label and arrows. If the unit is to be transported after
initial unpacking and inspection, place air conditioner back in
original packing to prevent damage.
For shipment, repack as received and re-band to the pallet.
Shipping without being strapped to the pallet may result in
tipping and damage and voids the warranty.
Air conditioners are not designed to be shipped attached to an
equipment enclosure. If this is required, the air conditioner must
have sufficient support to prevent damage due to vibration and
shock. Air conditioners damaged internally, due to being shipped
attached to enclosures, are warranty voided.
Inspecting the Equipment
STRATUS air conditioning equipment is designed,
manufactured and packed to prevent damage from normal
handling, shock and vibration during shipment. Please be sure
to inspect your equipment upon receipt to ensure that there is
no visual or hidden damage.
Upon receipt of the equipment, ensure that it is always top
side up as indicated by “THIS SIDE UP” labels; this ensures
that the compressor oil is not displaced. If the equipment has
been on its side, it must be put upright for at least 24 hours
before installing or running to be certain the compressor oil has
returned to the compressor. All physical damage to packing or
signs of damage to the equipment must be noted on the freight
bill of lading. Packages must be opened after receipt to inspect
for any internal /concealed damage to the equipment and to
verify proper count and order fulfillment. Shipments delivered
without the pallet, not top-side up, other freight on top,
damaged or wet should be refused delivery. Contact the
shipper immediately upon discovery of shipping damage to
schedule inspection by the freight company. Keep all packing.
AutomationDirect cannot take responsibility for customer’s
failure to file freight damage claims on a timely basis.
1000 - 1500 BTU/Hour Models
• 1 Pre-bagged Hanger Bolt Kit includes
(8) - 10-32 x 1/2 Machine Screws/ Unslotted /Indented Hex Washer Head, Steel/ Zinc
(8) - #10 Medium Split Lock Washer, Steel/Zinc
(8) - #10 Flat Washer/Machine Screw, Steel/Zinc
• Rubber Seal Gasket X-114HT Pre-Cut, QTY 6.5 feet. NEMA/UL Type 4 and 4X units have gasket installed
• Instruction / Operation Manual
• Actual Size Mounting Template
2000 - 4000 BTU/Hour Models
• 1 Pre-bagged Hanger Bolt Kit includes
(10) - 1/4 - 20 x 3/4 Machine Screws/ Unslotted/ Indented Hex Washer Head, Steel/Zinc
(10) - 1/4 Medium Split Lock Washers, Steel/Zinc
(10) - 1/4 Flat Washer/Machine Screw, Steel/Zinc
• Rubber Seal Gasket X-114HT Pre-Cut, QTY 8.5 feet. NEMA/UL Type 4 and 4X units have gasket installed
• Instruction / Operation Manual
• Actual Size Mounting Template
5000 - 8000 BTU/Hour Models
• 1 Pre-bagged Hanger Bolt Kit includes
(10) - 1/4 - 20 x 3/4 Machine Screws/ Unslotted/ Indented Hex Washer Head, Steel/Zinc
(10) - 1/4 Medium Split Lock Washers, Steel/Zinc
(10) - 1/4 Flat Washer/Machine Screw, Steel/Zinc
• Rubber Seal Gasket X-114HT Pre-Cut, QTY 10.0 feet. NEMA/UL Type 4 and 4X units have gasket installed
• Instruction / Operation Manual
• Actual Size Mounting Template
What’s in the box
Upon receipt of the STRATUS Air
Conditioner, please check for the following:
• Make sure that the box contains all items
required for installation of your series.
• Inspect the unit to ensure it was not
damaged during shipment.
• Make sure that the part number
indicated on the serial number label
corresponds with the part number of
your order.
Volts Amps
Phase
Hz 60
Refrigerant Ounces
Design Pressure:
Low Side
psi High Side
psi
Motor-Compressor Thermally Protected
UL Type 12, 04, 4X Interface to Electronic Enclosure per UL 50 & 508a
Special Purpose
Air Conditioner
S/N
MODEL No.
BTU
/H
NEMA Type
Automation Direct
•
800.633.0405
www.automationdirect.com
UL File # SA33404
Input Specification
Refrigerant Type/Weight
Refrigerant Pressure
Enclosure Rating
A/C Unit Serial Number
A/C Unit Model Number
Nameplate Information
Be sure to record the data from the label onto the back
of the manual and keep in a safe place for warranty.
WARNING: Before operating the air conditioner,
inspect all electrical wiring to ensure proper
installation and wiring to the proper power source.
The minimum circuit amperage must be 125% of the
air conditioner label amperage listed for the voltage
selected.