Room Requirements
3-6
Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide
(R624)
C A U T I O N
!
Due to the mission-critical nature of Stratus servers, data
centers housing the equipment should follow the
guidelines of airborne contamination (particulate and
gaseous) as outlined in the ASHRAE (TC) 9.9
documentation. Particulate matter to adhere to ISO
14644-1 Class 8. Gaseous contamination, such as sulfur
or chlorine-bearing gases to adhere to
ANSI/ISA-71.04-1985 Severity level G1.
M I S E E N G A R D E
!
En raison de la nature stratégique des serveurs Stratus,
les centres de données hébergeant l’équipement doivent
respecter les directives relatives à la contamination
atmosphérique (particulaire et gazeuse), tel qu’indiqué
dans la documentation 9.9 de l’ASHRAE (TC). Les
particules doivent adhérer à la norme ISO 14644-1
Classe 8. La contamination gazeuse, comme les gaz
chlorés ou sulfurifères, doit adhérer à la norme
ANSI/ISA-71.04-1985 avec un niveau de sévérité G1.
Dust buildup in the system can impede air circulation and heat transfer, causing
components to become less reliable as the ambient temperature rises.
Fans clogged by dust fail to expel hot air, causing circuit boards to overheat and
fail.
Dust on circuit boards raises the temperature, thus reducing the component's
mean time between failure (MTBF).
Dust circulating in the room increases the risk of fire within the room by providing
potential combustible material within the environment.
Dust contamination on tape devices causes mis-reads and -writes, leading to
failure of attempts to back up and restore data.
Has sufficient floor space for external components, such as the optional external
E124 storage-system cabinets
Provides a table or desktop for external devices such as a telephone, RSN console
server, RSN modem (if present), and a system PC console.
You
cannot
place these peripheral components in or on top of a system cabinet.
Содержание ftServer V 2302
Страница 1: ...Stratus Technologies R624 04 Stratus ftServer V 2302 V 4304 and V 6308 Systems Site Planning Guide ...
Страница 10: ...Preface x Stratus ftServer V 2302 V 4304 and V 6308 Systems Site Planning Guide R624 ...
Страница 47: ...Creating a Floor Plan Space and Component Location Planning 3 11 Figure 3 3 Site Layout Grid 1 square foot ...
Страница 48: ...Creating a Floor Plan 3 12 Stratus ftServer V 2302 V 4304 and V 6308 Systems Site Planning Guide R624 ...
Страница 64: ...AAP87600V PDU Specifications A 8 Stratus ftServer V 2302 V 4304 and V 6308 Systems Site Planning Guide R624 ...