PDU Safety Considerations
B-10
Stratus ftServer 29x0, 49x0, and 69x0 Systems: Site Planning and Installation Guide
(R786)
PDU Safety Considerations
This section describes some important safety considerations for PDUs.
A PDU provides for the reliable distribution of power via eight outlets. When installed
into a standard EIA 19-inch data, security, or industrial control rack, the PDU provides
up to 3.84 kilowatts of filtered power to the system.
The PDU’s input is filtered to reduce emissions in Information Technology (IT)
applications and provides at least 30 decibels of common-mode noise reduction. It
provides even greater differential noise reduction between the frequency ranges of
1 to 10 MHz. In addition, the PDU contains thermally protected transient voltage
suppression (TVS) networks, which clamp common mode and differential mode
voltage transients with up to 170 joules of energy content. The PDU is also equipped
BS 1363/A
13A, 250 volts AC
2-pole, 3-wire
SEV
1011-S24507
10A, 250 volts AC
2-pole, 3-wire
SAA/3/15
AS/NZS
3112-1993
15A, 250 volts AC
2-pole, 3-wire
GB1002-1996
10A, 250 volts AC
2 pole, 3-wire
Table B-1. Connectors for AC Power Outlets
(Continued)
Connector Configuration
Rating
Description