Ethernet Cables
4-6
Stratus ftServer 2600, 4500, and 6300 Systems: Site Planning Guide (R638)
Table 4-2. Customer-Supplied Ethernet Cables
Component
Quantity
Marketing ID/Cable
Length
Cable Type
VTM Ethernet port
2
N/A. You must
supply these cables.
The maximum
allowable distance
from these ports to a
switch or a hub is
328 ft (100m).
24 AWG Unshielded Twisted Pair
(UTP) EIA/TIA-Verified, Category-3
or Category-5 wire, with RJ-45
modular connectors terminated with
pair-wiring adhering to the EIA/TIA
568-A or EIA/TIA 568-B standard.
For connections to an Ethernet hub
or switch, provide a straight-through
cable.
For 100- or 1000-Mbps (fast
Ethernet) operation, provide
full-duplex, or Category-5 Ethernet
cables.
System Ethernet port
2 or 4
U105 Dual-Port
Copper 10/100/1000
Base-T Ethernet
PCI-Express Adapter
(gigabit copper
adapter for servers)
1 for each
port, typically
teamed for
fault
tolerance
U104 Dual-Port Fiber
Gigabit Ethernet
PCI-Express Adapter
(gigabit fiber-optic
adapter for servers)
1 for each
port, typically
teamed for
fault
tolerance
N/A. You must
supply these cables.
The maximum
distance between
the U104 PCIe
adapter and a switch
is 902 ft (275m).
Multimode, 62.5- or 50-micron,
DUAL fiber cable with LC-type
connectors to the PCIe adapter,
and connectors on the other end
that are compatible with your site
network switch.
U108 Single-Port
Fiber 10-Gigabit
Ethernet
PCI-Express
Adapter
†
(Linux
systems only)
1, typically
teamed for
fault
tolerance
N/A. You must
supply this cable.
The maximum
distance between
the U108 PCIe
adapter and a switch
is 282 ft (86 m) for
62.5-micron
multimode fibre
(MMF) and 1804 ft
(550 m) for
50-micron MMF,
depending on the
grade of the cable
Multimode, 62.5- or 50-micron,
10GBase-SR DUAL fiber cable with
LC-type connectors to the PCIe
adapter, and connectors on the
other end that are compatible with
your site network switch.
Содержание ftServer 2600
Страница 1: ...Stratus Technologies R638 02 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide...
Страница 8: ...Tables viii Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 44: ...Grounding Requirements 2 16 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 48: ...Planning for Cables 3 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 64: ...Example of PDU Usage Calculation 5 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 70: ...Monitor Requirements 6 6 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 80: ...AAP87600 PDU Specifications A 10 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...
Страница 98: ...Index Index 4 Stratus ftServer 2600 4500 and 6300 Systems Site Planning Guide R638...