Cartridge Types
8-4
StorageTek SL8500 User's Guide
Exporting Diagnostic or Cleaning Cartridges
1.
Verify that the library has enough empty system slots. Robot recovery and library
initialization requires one empty system slot on each side of the library.
2.
Verify that the CAP is empty, not reserved by a host, closed, and locked (see
"Viewing Device Status and Properties"
3.
In SLC, select
Tools > Diagnostics
.
4.
Expand the
CAP
folder in the device tree. Select a
CAP
to use.
5.
Click the
Import/Export
tab.
6.
Select the type of export operation.
7.
Click
Start
.
8.
When the unload notification appears, unload the CAP (see
Cartridge Types
■
Data cartridges — store customer data.
■
Diagnostic cartridges — used by service representatives to run read/write tests on
drives (see
"Importing or Exporting Diagnostic or Cleaning Cartridges"
■
Cleaning cartridges — clean the tape path and read/write heads of the tape drives
(see
Cartridge Labels
For information about media label standards, see the
Barcode Technical Brief
on OTN.
All library cartridges must have a readable external label. The robot reports an error
when it encounters an unreadable label.
Non-labeled cartridges are not supported. The library exports any non-labeled
cartridges it finds through the CAP. A non-labeled or unknown type cartridge will not
mount to a drive.
Handling Cartridges
■
Keep cartridges clean and inspect them for damage before each use.
■
Never open a cartridge.
■
Do not handle tape that is outside the cartridge.
■
Do not expose the tape or cartridge to direct sunlight, moisture, or magnetic fields.
Inspecting a Cartridge
Always inspect a cartridge before you insert it into a tape drive or a library. A
defective or dirty cartridge can damage a tape drive. Never use a damaged cartridge.
Look for:
Caution:
When cartridges are improperly handled, loss of data or
damage to a library component can occur.
Содержание SL8500
Страница 1: ...1 StorageTek SL8500 User s Guide E20869 12 March 2017...
Страница 12: ...xii...
Страница 16: ...Installing Web launched SLC 1 4 StorageTek SL8500 User s Guide...
Страница 22: ...Enabling Features on a Library with Firmware Before FRS_7 00 3 4 StorageTek SL8500 User s Guide...
Страница 26: ...Effect on HLI Hosts after Modifying the Capacity Configuration 4 4 StorageTek SL8500 User s Guide...
Страница 32: ...Maximizing Library Performance when Partitioning 5 6 StorageTek SL8500 User s Guide...
Страница 38: ...Guidelines for using CAPs 6 6 StorageTek SL8500 User s Guide...
Страница 46: ...Maximizing Library Performance Though Cartridge Placement 8 6 StorageTek SL8500 User s Guide...
Страница 62: ...Monitoring Library Events 12 6 StorageTek SL8500 User s Guide...
Страница 66: ...Rebooting a Robot 13 4 StorageTek SL8500 User s Guide...
Страница 80: ...A 2 StorageTek SL8500 User s Guide...
Страница 94: ...whereAmi B 14 StorageTek SL8500 User s Guide...
Страница 108: ...Firmware Upgrades with RE D 4 StorageTek SL8500 User s Guide...
Страница 138: ...World Wide Name Glossary 10...