![Stober SD6 Series Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/stober/sd6-series/sd6-series_operating-manual_1381247014.webp)
6 | Connection
STOBER
14
02/2020 | ID 442516.07
6
Connection
In order to connect the EC6 communication module of the SD6 drive controller to other EtherCAT nodes, the top of each
device features two RJ-45 sockets.
6.1
Selecting suitable lines
EtherCAT is an Ethernet-based communications technology optimized for automation technology.
Ethernet patch cables or crossover cables meeting the CAT 5e quality level are the ideal cables. The Fast Ethernet
technology allows a maximum cable length of 100 m between two nodes.
Information
Ensure that you only use shielded cables with an SF/FTP, S/FTP or SF/UTP design.
6.2
X200, X201: Fieldbus connection
The drive controllers have both RJ-45 sockets X200 and X201. The sockets are located on top of the device. The associated
pin assignment and color coding correspond to the EIA/TIA-T568B standard.
Socket
Pin
Designation
Function
1|2| ... |7|8
1
Tx+
Communication
2
Tx−
3
Rx+
4
—
—
5
—
—
6
Rx−
Communication
7
—
—
8
—
—
Tab. 1: X200 and X201 connection description